7 command #137 reset totalizers – KROHNE UFC 500 HART User Manual

Page 21

Advertising
background image

HARTô Smart Communications Protocol

UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001

© 2001 KROHNE Mefltechnik D-47058 Duisburg

Page

21

8.7

Command #137

Reset Totalizers

Clears (sets to zero) either any of the two totalizers (positive and negative) or both of them.

REQUEST DATA BYTES

#0
TOTALIZER
RESET
CONTROL

RESPONSE DATA BYTES

#0
TOTALIZER
RESET
CONTROL

Data Byte #0

A control variable, selecting totalizer(s) to be reset:
1 - positive totalizer,
2 - negative totalizer,
3 - both totalizers, i.e. Totalizersí Sum variable.

NOTE: Response Code 16, Access Restricted, is returned when EnableReset control variable (Menu 3.5.10) is set to
ìNoî. Refer to Commands #148/#149, Read/Write User-Defined Unit and Auxiliary Controls.

COMMAND-SPECIFIC RESPONSE CODES

0

No Command-Specific Errors

1

Undefined

2

Invalid Selection (of Totalizer)

3-4

Undefined

5

Too Few Data Bytes Received

6

Local Device User

7

In Write Protect Mode

8-15

Undefined

16

Access Restricted

17-127

Undefined