KROHNE UFC 500 HART User Manual

Page 19

Advertising
background image

HARTô Smart Communications Protocol

UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001

© 2001 KROHNE Mefltechnik D-47058 Duisburg

Page

19

8.5

Command #134

Read Analog Output Low Flow Cutoff Control And Values

Reads low flow cutoff parameters of the requested output.

REQUEST DATA BYTES

#0
ANALOG
OUTPUT
NUMBER
CODE

RESPONSE DATA BYTES

#0

#1

#2

#3

ANALOG CUTOFF

CUTOFF

CUTOFF

OUTPUT

CONTROL

ON

OFF

NUMBER

VALUE

VALUE

CODE

Data Byte #0

Analog Output Number Code, equals м1о for current output and м2о - for pulse output.

Data Byte #1

Cutoff control variable:
0 - cutoff option is switched On ,
1 - cutoff option is switched Off.

Data Byte #2

Cutoff On Value, in % of the Primary Variable Upper Range Value. When cutoff is switched
Off (Data Byte #1 = 1), the instrument still uses the cutoff option, but with defaulted On
Value, namely 0.1%. Nevertheless, bus master will be presented with the On Value, that is
stored in EEPROM, but is not currently in use.

Data Byte #3

Cutoff Off Value, in % of the Primary Variable Upper Range Value. When cutoff is switched
Off (Data Byte #1 = 1), the instrument still uses the cutoff option, but with defaulted Off
Value, namely 0.25%. Nevertheless, bus master will be presented with the Off Value, that is
stored in EEPROM, but is not currently in use.

COMMAND-SPECIFIC RESPONSE CODES

0

No Command-Specific Errors

1

Undefined

2

Invalid Selection

3-4

Undefined

5

Too Few Data Bytes Received

6

Local Device User

7-127

Undefined

Advertising