Instantaneous value measurement: w range, Instantaneous value measurement – KYORITSU 6300 Quick Manual User Manual

Page 11

Advertising
background image

W

range

Safety first!

Turning on the instrument

Basic setting

Wiring

Instantaneous value

measurement

5. Instantaneous value measurement:

W

range

(Section 6)

● Measurement flow chart

● Displayed items on

W

range

Displayed parameters

Unit

Voltage (RMS) V : Average voltage of Vi

Vi : Voltage per phase

V

Current (RMS) A : Average current of Vi

Ai : Current per phase

A

Active power

P : Total active power

Pi : Active power per phase

Polarity: + (no mark) consumption,

- (minus) regenerating

W

Reactive power Q : Total reactive power

Qi : Reactive power per phase

Polarity: + (no mark) phase lag,

- (minus) phase lead

Var

Apparent power S : Total apparent power

Si : Apparent power per phase

VA

Power factor

PF : Total power factor

Pfi : Power factor per phase

Polarity: + (no mark) phase lag,

- (minus) phase lead

PF

Frequency

f : Frequency at V1

Hz

Neutral current In

**

: Current on a neutral line (only at three-phase 4-wire)

An

* i = 1, 2, 3

** :

The recorded/displayed In(neutral current) value will not be a true value in situations where

there is an earth leakage or leakage current flowing through the live conductors of the three

phase system that is being monitored using the Power Meter Model 6300.

SET UP

range

“ Setting 01” Wiring

“ Setting 02” Voltage range

“ Setting 03” Current range

“ Setting 04” Clamp sensor

“ Setting 05” VT ratio (if necessary)

“ Setting 06” CT ratio (if necessary)

− 9 −