RELAY PARAMETERS

Each relay can be individually calibrated. Press

È to

R Function

and

Æ to select:

Off

Æ

Pulse

Æ

Temp

Æ

Level

Æ

Flow.

Off

mode means the relay will not be energized

Pulse

Appears in Flow mode only. Press

È and set digits to the flow volume increment required

between relay pulses. Use this feature for remote samplers, chlorinators or totalizers.
Minimum time between pulses is 1 second and pulse duration is 350 milliseconds.

Temp

References temperature reading from the Ultrason's ultrasonic sensor (air temperature at
the sensor location). Press

È and Æ and set the relay On and Off set points.

Level

Range

Volume

Appears in Level, Range, Volume or HRT modes only. Press

È to

R Function

and

Æ

to select

Pump

,

LoAlm

(low alarm) or

HiAlm

(high alarm).

Pump

mode

- press

È and Æ and set relay On and Off set points.

LoAlm

mode

- press

È and set relay On point. Relay will be On with levels below

this point.

HiAlm

mode

- press

È and set relay On point. Relay will be On with levels above

this point.

LOE

- press

Æ to select

Off

Æ

On

Æ

Hold

. In a loss of echo condition, the

(Loss Of Echo) relay will turn Off (de-energize), On (energize) or Hold its current state.

Each relay can be individually configured. Press

È.

To calibrate a relay for echo loss alarm only, set the relay On and Off set points to exactly
the same value, and then set

LOE

to

On

mode. The relay will now energize only when an

echo loss condition occurs.

AquaMetrix

Ultrason

Page 13

CALIBRATION

SPECIAL FUNCTION

RELAY PARAMETERS

Pulse

Temp

R1 Function Off

R1on 0.00 ft3

R1on 0.00 C

°

R1

0.00

OFF

° C

R2 Function Off

Level

Flow

R1 Mode Pump

LoAlm

HiAlm

R1 on 0.00 ft

R1 on 0.00ft3/s

R1 OFF 0.00 ft

R1 LOE Off

On

Pulse

Temp

Level

Flow

Hold