RS485 SERIAL OUTPUT
(Replaces standard RS232 Output with Data Logger option.)

Permits transfer of optional Data Logger reports on long wire lengths up to 4000 ft. (1220 m). Use for
Ultrason to PC communication only (not for multidrop RS485 networking).
Format: 8 Bits, 1 Stop Bit, No Parity. (Baud rate may be changed under the

SPECIAL FUNCTIONS

menu. Factory default is 19200 baud).

Use shielded, 4-conductor cable (cable option SC-18AWG recommended). Connect the cable shield to
Ground at the Ultrason electronics enclosure and do not connect to Ground at the other end.

Configure the Logger software program for RS485 communications. Under the Communications /
Connection Setup menu, select 'Connected to a 485OICR-12V adaptor.

485OICR-12V
RS232/RS485 Converter

Use with optional RS485 putput for connection to a PC computer
or modem.

• Optically isolates and protects your computer's RS232 port
• Terminal block for RS485 connections
• Operates from 2400 up to19.2K baud

DB25M/DB9F - RS232 Cable
Connects RS232/485 Converter to a PC

Cable length 6 ft.(2 m) with DB25M and DB9F connectors.

Page 39

AquaMetrix

Ultrason

A

M

qua etrix

Transmitter

with

RS485 Output

RS485

<4000 ft (1220 m)

Detail

RX

RS485

PU GND TX

(GREEN)

(WHT)

(BLK)

(RED)

18AWG, 4-conductor, shielded

Option: SC-18AWG

RS485

RS232

DB25F

RS232/485 Converter

Option: 485OICR-12V

DB9F

DB25M

RS232 Cable

Option: DB25M/DB9F

TX

RX
PU

GND

6 ft (2 m)