A qua m etrix – Metex 3200U Ultrasonic Flow & Level Monitor User Manual
Page 14

Flow
Appears in Flow mode only. Press
È to
R Function
and
Æ to select
Pump
,
LoAlm
(low alarm) or
HiAlm
(high alarm).
Pump
mode
- press
È and Æ and set relay On and Off set point.
LoAlm
mode
- press
È and set relay On point. Relay will be energized with levels
below the On point and de-energized with levels above the On point.
HiAlm
mode
- press
È and set relay On point. Relay will be energized with levels
above the On point and de-energized with levels below the On point.
LOE
- press
Æ to select
Off
Æ
On
Æ
Hold
. In a loss of echo condition, the
(Loss Of Echo) relay will turn Off (de-energize), On (energize) or Hold its current state.
Each relay can be individually configured. Press
È.
ALT
permits relays calibrated in Pump mode to be
alternated automatically. Pump alternation
allows even pump wear in pumping station
applications.
ALT
(-None-) indicates that no relays have
been programmed in Pump mode.
ALT 123
- Press
Æ to place cursor (underline)
under the relay number to be programmed for
alternation and press
Ç or È to highlight.
Repeat until all relays to be alternated are
highlighted.
Press
È to
Store? Yes
and
Æ to
Yes
. Press
Ç or È to save your Relay settings.
AquaMetrix
Ultrason
Page 14
PUMP ALTERNATION (R1, R2, R3)
LEAD
PUMP
LAG
PUMP 1
LAG
PUMP 2
1st CYCLE
2nd CYCLE
3rd CYCLE
...ETC
1
2
2
3
3
1
3
1
2