A qua m etrix – Metex 3200U Ultrasonic Flow & Level Monitor User Manual

Page 14

Advertising
background image

Flow

Appears in Flow mode only. Press

È to

R Function

and

Æ to select

Pump

,

LoAlm

(low alarm) or

HiAlm

(high alarm).

Pump

mode

- press

È and Æ and set relay On and Off set point.

LoAlm

mode

- press

È and set relay On point. Relay will be energized with levels

below the On point and de-energized with levels above the On point.

HiAlm

mode

- press

È and set relay On point. Relay will be energized with levels

above the On point and de-energized with levels below the On point.

LOE

- press

Æ to select

Off

Æ

On

Æ

Hold

. In a loss of echo condition, the

(Loss Of Echo) relay will turn Off (de-energize), On (energize) or Hold its current state.

Each relay can be individually configured. Press

È.

ALT

permits relays calibrated in Pump mode to be
alternated automatically. Pump alternation
allows even pump wear in pumping station
applications.

ALT

(-None-) indicates that no relays have

been programmed in Pump mode.

ALT 123

- Press

Æ to place cursor (underline)

under the relay number to be programmed for
alternation and press

Ç or È to highlight.

Repeat until all relays to be alternated are
highlighted.

Press

È to

Store? Yes

and

Æ to

Yes

. Press

Ç or È to save your Relay settings.

AquaMetrix

Ultrason

Page 14

PUMP ALTERNATION (R1, R2, R3)

LEAD
PUMP

LAG

PUMP 1

LAG

PUMP 2

1st CYCLE

2nd CYCLE

3rd CYCLE

...ETC

1

2

2

3

3

1

3

1

2