R-lo f1, R-lo usr-1 r-hl usr-1 r-hl f1, D-lev usr-1 d-lev f1 – NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual

Page 14: Disp usr-1, Dsp-a usr-1, Dsp-b usr-1, Dsp-c usr-1, Dsp-_ usr-1, List usr-1 list f1, Print usr-1 print f1

Advertising
background image

14

RESET MINIMUM

r-Lo

F1

When activated (momentary action),

rESEt

flashes and the Minimum reading

is set to the present assigned value. The Minimum function then continues from
that value. This selection functions independent of the selected display.

r-Lo

USr-1

r-HL

USr-1

r-HL

F1

RESET MAXIMUM AND MINIMUM

When activated (momentary action),

rESEt

flashes and the Maximum and

Minimum readings are set to the present assigned values. The Maximum and
Minimum function then continues from that value. This selection functions
independent of the selected display.

d-LEV

USr-1

d-LEV

F1

CHANGE DISPLAY INTENSITY LEVEL

When activated (momentary action), the display intensity changes to the next

intensity level (of 4). The four levels correspond to Display Intensity Level (

d-

LEv

) settings of 0, 3, 8, and 15.

Note: Following display functions are only available on User Input.

dISP

Usr-1

ADVANCE DISPLAY

When activated (momentary action), the display advances to the next display

that is not locked out from the Display Mode.

dSP-a

Usr-1

SELECT DISPLAY A

When activated (momentary action), the display advances to Display A,

if enabled.

dSP-b

USr-1

SELECT DISPLAY B

When activated (momentary action), the display advances to Display B,

if enabled.

dSP-C

Usr-1

SELECT DISPLAY C

When activated (momentary action), the display advances to Display C,

if enabled.

dSP-_

Usr-1

SELECT DISPLAY _

When activated (momentary action), the display advances to the Display _

(no annunciator), if enabled.

LISt

USr-1

LISt

F1

EXCHANGE PARAMETER LISTS

Two lists of values are available for

SP-1

,

SP-2

,

SP-3

,

SP-4

. The two lists are

named

LSt-A

and

LSt-b

. If a user input is used to select the list then

LSt-A

is

selected when the user input is not active and and

LSt-b

is selected when the

user input is active (maintained action). If a front panel key is used to select the
list then the list will toggle for each key press (momentary action). The display
will only indicate which list is active when the list is changed.

To program the values for

LSt-A

and

LSt-b

, first complete the programming

of all the parameters. Exit programming and switch to the other list. Re-enter
programming and enter the values for

SP-1

,

SP-2

,

SP-3

,

SP-4

. If any other

parameters are changed then the other list values must be reprogrammed.

SETPOINT SELECTIONS

LISt

-

Select main or alternate setpoints

r-1

-

Reset Setpoint 1 (Alarm 1)

r-2

-

Reset Setpoint 2 (Alarm 2)

r-3

-

Reset Setpoint 3 (Alarm 3)

r-4

-

Reset Setpoint 4 (Alarm 4)

r-34

-

Reset Setpoint 3 & 4 (Alarm 3 & 4)

r-234

-

Reset Setpoint 2, 3 & 4 (Alarm 2, 3 & 4)

r-ALL

-

Reset Setpoint All (Alarm All)

The following selections are functional only with the Setpoint plug-in card

installed. Refer to the Setpoint Card Bulletin shipped with the Setpoint plug-in
card for an explanation of their operation.

Setpoint

Card

Only

Print

USr-1

Print

F1

PRINT REQUEST

The meter issues a block print through the serial port when activated, and the

serial type is set to

rLC

. The data transmitted during a print request and the serial

type is programmed in Module 7. If the user input is still active after the
transmission is complete (about 100 msec), an additional transmission occurs.
As long as the user input is held active, continuous transmissions occur.