NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual

Page 25

Advertising
background image

25

REGISTER

ADDRESS

1

REGISTER NAME

LOW LIMIT

2

HIGH LIMIT

2

FACTORY

SETTING

ACCESS

COMMENTS

40406

40396

40386

40412

40402

40392

40382

Transmit Delay

Output Logic

Output Logic

Assignment

Baud Rate

Action

Action

0

0

0

0

0

0

0

250

1

1

8

7

10

10

10

0

0

0

7

0

0

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

1=0.001 Second

0=Normal, 1=Reverse

0=Normal, 1=Reverse

0=NONE, 1=A-REL, 2=A-AbS, 3=b-rEL, 4=b-AbS,
5=CALC, 6=tot, 7=HI, 8=LO

0=300, 1=600, 2=1200, 3=2400, 4=4.8k, 5=9.6k,
6=19.2k, 7=38.4k

0=No, 1=Ab-HI, 2=Ab-Lo, 3=AU-HI, 4=AU-LO, 5=dE-HI,
6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI

0=No, 1=Ab-HI, 2=Ab-Lo, 3=AU-HI, 4=AU-LO, 9=totLo,
10=totHI; Do not use 5-8.

40411

40401

40391

40381

Type

Type

Assignment

Assignment

0

0

0

0

2

2

6

6

1

2

0

0

Read/Write

Read/Write

Read/Write

Read/Write

0 = 0-20 mA, 1 = 4-20 mA, 2 = 0-10 V

0=RLC Protocol, 1=Modbus RTU, 2=Modbus ASCII

ANALOG OUTPUT PARAMETERS

SERIAL COMMUNICATIONS PARAMETERS

SETPOINT 4 OUTPUT PARAMETERS

SETPOINT 3 OUTPUT PARAMETERS

40409

40399

40389

40405

40395

40385

Load Serial Settings

Lit - Annunciator

Lit - Annunciator

Address

Off Delay

Off Delay

0

0

0

1

0

0

0

1

3

3

247

99

32750

32750

0

1

1

247

0

0

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

0=Off, 1=Normal, 2=Reverse, 3=Flash

0=Off, 1=Normal, 2=Reverse, 3=Flash

Modbus: 1-247

RLC Protocol: 0-99

1=0.1 Second

1=0.1 Second

40408

40398

40388

40416

40414

40404

40394

40384

Print Options

Standby

Standby

Analog High Value (Lo word)

Analog Low Value (Lo word)

Parity

On Delay

On Delay

0

0

0

0

0

0

63

1

1

2

32750

32750

0

0

0

0

0

0

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

0=No, 1 = Yes

0=No, 1 = Yes

0=None, 1=Even, 2=Odd

1=0.1 Second

1=0.1 Second

40417

40407

40397

40387

40415

40413

40403

40393

40383

Reset

Reset

Analog High Value (Hi word)

Analog Low Value (Hi word)

Data Bits

Hysteresis

Hysteresis

SEE MODULE 7 FOR DESCRIPTION OF PARAMETERS

0

0

0

0

-19999

-19999

0

1

1

100

1

2

2

99999

99999

1

65000

65000

0

0

0

10000

0

1

2

2

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

0=Max update rate, 1=0.1 second

0=No, 1=Yes
Not used when communications type is Modbus

0=Auto, 1=Latch1, 2=Latch2

0=Auto, 1=Latch1, 2=Latch2

0=7 bits, 1=8 bits

1=1 Display Unit

1=1 Display Unit

6=Tot

5=Calc

4=bAbs

3=b-Rel

2=A-Abs

1=A-Rel

0=None

6=Tot

5=Calc

4=bAbs

3=b-Rel

2=A-Abs

1=A-Rel

0=None

Update Time

Abbreviated Transmission (RLC
only)

0=No, 1=Yes
Not used when communications type is Modbus
Bit 0 - Print Input A Value
Bit 1 - Print Input B Value
Bit 2 - Print CALC Value
Bit 3 - Print Max & Min Values
Bit 4 - Print Total Value
Bit 5 - Print Setpoint Values

Changing 40401-40406 will not update until
this register is written with a 1. After the write, the
communicating device must be changed to the new
settings and the register returns to 0.

SEE MODULE 8 FOR DESCRIPTION OF PARAMETERS
(APPLIES ONLY WHEN LINEAR OUTPUT CARD,
IS INSTALLED)

Display value that corresponds with 10 V or
20 mA output

Display value that corresponds with 0 V, 0 mA or
4 mA output

1

For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.

2

An attempt to exceed a limit will set the register to its high or low limit value.