3

G

ENERAL

M

ETER

S

PECIFICATIONS

1.

DISPLAY: 5 digit, 0.56" (14.2 mm) variable intensity red sunlight readable

(-19999 to 99999)

2. POWER:

AC Versions:

AC Power: 85 to 250 VAC, 50/60 Hz, 21 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.

DC Versions: (Derate operating temperature to 40° C if three plug-in option

cards is installed.)
DC Power: 18 to 36 VDC, 13 W
AC Power: 24 VAC, ± 10%, 50/60 Hz, 16 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).

3. ANNUNCIATORS:

A - Programmable Display
B - Programmable Display
C - Programmable Display
SP1 - Setpoint alarm 1 is active
SP2 - Setpoint alarm 2 is active
SP3 - Setpoint alarm 3 is active
SP4 - Setpoint alarm 4 is active
Units Label - Optional units label backlight

4. KEYPAD: 3 programmable function keys, 5 keys total
5. A/D CONVERTER: 16 bit resolution
6. UPDATE RATES:

A/D conversion rate: adjustable 5.3 to 105 readings/sec.
Step response: (to within 99% of final readout value with digital filter disabled)

Display update rate: adjustable 1 to 20 readings/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec.

7. DISPLAY MESSAGES:

“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
“. . . .” - Appears when display values exceed + display range.
“- . . .” - Appears when display values exceed - display range.

8. SENSOR INPUTS:

* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over

an 18 to 28

°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C

and 0 to 85% RH (non-condensing environment). Accuracy over the 0 to
50

°C range includes the temperature coefficient effect of the meter.

9. EXCITATION POWER:

Transmitter Power: 18 VDC,

±20%, unregulated, 70 mA max. per

input channel.

10. LOW FREQUENCY NOISE REJECTION:

Normal Mode: (digital filter off)

*Note: 19.8 Hz Input Rate provides best rate performance and

simultaneous 50/60 Hz rejection.

Common Mode: >100 dB @ 50/60 ±1 Hz (19.8 or 20 Input Rate)

11. USER INPUTS: Three programmable user inputs

Max. Continuous Input: 30 VDC
Isolation To Sensor Input A Common: 500 Vrms for 1 min;

Working Voltage: 50 V

Isolation To Sensor Input B Common: Not isolated.

Response Time: 20 msec. max.
Logic State: Jumper selectable for sink/source logic

12. TOTALIZER:

Function:

Time Base: second, minute, hour, or day
Batch: Can accumulate (gate) input display from a user input

Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts

13. CUSTOM LINEARIZATION:

Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000

14. MEMORY: Nonvolatile memory retains all programmable parameters and

display values.

15. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in

option cards installed)

Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters

V

IN

> 3.6 VDC

V

IN

< 0.9 VDC

Inactive

V

IN

< 0.9 VDC

V

IN

> 3.6 VDC

Active

SINKING INPUTS

22 K

Ω pull-up to +5 V

SOURCING INPUTS

22 K

Ω pull-down

INPUT STATE

INPUT

(RANGE)

ACCURACY*

(18 to 28°C)

ACCURACY*

(0 to 50°C)

IMPEDANCE/

COMPLIANCE

MAX

CONTINUOUS

OVERLOAD

DISPLAY

RESOLUTION

±20 mA

(-26 to

26 mA)

0.03% of

reading +2

μA

0.12% of

reading +3

μA

24.6 ohm

150 mA

1

μA

±10 VDC

(-13 to

13 VDC)

0.03% of

reading +2 mV

0.12% of

reading +3 mV

500 Kohm

50 V

1 mV

Input Update Rate

Max. Time (msec)

5.3

770

7.5

560

16.7

260

19.8

220

20

220

30

150

105

60

Input Update Rate

50Hz ±1Hz

60Hz ±1Hz

5.3

>90 dB

>65 dB

7.5

>60 dB

>55 dB

16.7

>100 dB

>50 dB

19.8*

>60 dB

>95 dB

20

>55 dB

>100 dB

30

>20 dB

>20 dB

105

>20 dB

>13 dB

Advertising