5

WARNING: Disconnect all power to the unit before

installing Plug-in cards.

Adding Option Cards

The 2100 series meters can be fitted with up to three optional plug-

in cards. The details for each plug-in card can be reviewed in the specification
section below. Only one card from each function type can be installed at one time.
The function types include Setpoint Alarms , Communications

and Analog Output . The plug-in cards can be installed initially or at a later date.

COMMUNICATION CARDS

A variety of communication protocols are available for the 2100

series. Only one of these cards can be installed at a time. Note: For Modbus
communications use RS485 Communications Output Card and configure
communication (

tYPE) parameter for Modbus.

SERIAL COMMUNICATIONS CARD

Type: RS485 or RS232
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Baud: 300 to 38,400
Data: 7/8 bits
Parity: no, odd or even
Bus Address: Selectable 0 to 99, (RLC Protocol) or 1 to 247 (Modbus

Protocol), Max. 32 meters per line (RS485)

Transmit Delay: Selectable for 0 to 0.250 sec (+2 msec min)

DEVICENET™ CARD -

2100

Compatibility: Group 2 Server Only, not UCMM capable
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per

DeviceNet™ Volume I Section 10.2.2.

Node Isolation: Bus powered, isolated node
Host Isolation: 500 Vrms for 1 minute (50 V working) between DeviceNet™

and meter input common.

PROFIBUS-DP CARD -

2100

Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens

SPC3 ASIC

Conformance: PNO Certified Profibus-DP Slave Device
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
Station Address: 0 to 126, set by the master over the network. Address

stored in non-volatile memory.

Connection: 9-pin Female D-Sub connector
Network Isolation: 500 Vrms for 1 minute (50 V working) between Profibus

network and sensor and user input commons. Not isolated from all other
commons.

SETPOINT CARDS

The 2100 series has 4 available setpoint alarm output plug-in

cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:

2100 - Dual Relay, FORM-C, Normally open & closed
2100 - Quad Relay, FORM-A, Normally open only
2100 - Isolated quad sinking NPN open collector
2100 - Isolated quad sourcing PNP open collector

DUAL RELAY CARD -

2100

Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.

Working Voltage: 240 Vrms

Contact Rating:

One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),

1/8 HP @120 VAC, inductive load

Total current with both relays energized not to exceed 5 amps

Life Expectancy: 100 K cycles min. at full load rating. External RC snubber

extends relay life for operation with inductive loads

QUAD RELAY CARD -

2100

Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.

Working Voltage: 250 Vrms

Contact Rating:

One Relay Energized: 3 amps @ 240 VAC or 30 VDC (resistive load), 1/10

HP @120 VAC, inductive load

Total current with all four relays energized not to exceed 4 amps

Life Expectancy: 100 K cycles min. at full load rating. External RC snubber

extends relay life for operation with inductive loads

QUAD SINKING OPEN COLLECTOR CARD -

2100

Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Rating: 100 mA max @ V

SAT

= 0.7 V max. V

MAX

= 30 V

QUAD SOURCING OPEN COLLECTOR CARD -

2100

Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Rating: Internal supply: 24 VDC ± 10%, 30 mA max. total

External supply: 30 VDC max., 100 mA max. each output

ALL FOUR SETPOINT CARDS

Response Time: See update rates step response specification; add 6 msec

(typical) for relay card

LINEAR DC OUTPUT

Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available

from the analog output plug-in card. The programmable output low and high
scaling can be based on various display values. Reverse slope output is possible
by reversing the scaling point positions.

2100 - Retransmitted Analog Output Card

ANALOG OUTPUT CARD

Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.

Working Voltage: 50 V. Not Isolated from all other commons.

Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C)
Resolution: 1/3500
Compliance: 10 VDC: 10 K

Ω load min., 20 mA: 500 Ω load max.

Update time: See update rates step response specification

O

PTIONAL

P

LUG

-

IN

O

UTPUT

C

ARDS

2100 - RS485 Serial (Terminal Block)

2100 - DeviceNet

2100 - RS232 Serial (Terminal Block)

2100 - RS485 Serial (Dual RJ11 Connector)

2100 - Profibus-DP

2100 - RS232 Serial (9 Pin D Connector)