8 module 8 - a, Nalog, Utput – NOSHOK 2100 Series Field Upgradeable Dual Input Process Indicator User Manual

Page 29: Arameters, Type, Asin, An-lo, An-hi

Advertising
background image

29

COMMUNICATION FORMAT

Data is transferred from the meter through a serial communication channel.

In serial communications, the voltage is switched between a high and low level
at a predetermined rate (baud rate) using ASCII encoding. The receiving device
reads the voltage levels at the same intervals and then translates the switched
levels back to a character.

The voltage level conventions depend on the interface standard. The table

lists the voltage levels for each standard.

Data is transmitted one byte at a time with a variable idle period between

characters (0 to

∞). Each ASCII character is “framed” with a beginning start bit,

an optional parity bit and one or more ending stop bits. The data format and
baud rate must match that of other equipment in order for communication to
take place. The figures list the data formats employed by the meter.

Start bit and Data bits

Data transmission always begins with the start bit. The start bit signals the

receiving device to prepare for reception of data. One bit period later, the least
significant bit of the ASCII encoded character is transmitted, followed by the
remaining data bits. The receiving device then reads each bit position as they are
transmitted.

Parity bit

After the data bits, the parity bit is sent. The transmitter sets the parity bit to

a zero or a one, so that the total number of ones contained in the transmission
(including the parity bit) is either even or odd. This bit is used by the receiver
to detect errors that may occur to an odd number of bits in the transmission.
However, a single parity bit cannot detect errors that may occur to an even
number of bits. Given this limitation, the parity bit is often ignored by the
receiving device. The meter ignores the parity bit of incoming data and
sets the parity bit to odd, even or none (mark parity) for outgoing data.

Stop bit

The last character transmitted is the stop bit. The stop bit provides a single bit

period pause to allow the receiver to prepare to re-synchronize to the start of a
new transmission (start bit of next byte). The receiver then continuously looks
for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2
stop bits are sent from the 2100.

Character Frame Figure

LOGIC

RS232*

RS485*

INTERFACE STATE

1

TXD,RXD; -3 to -15 V

a-b < -200 mV

mark (idle)

0

TXD,RXD; +3 to +15 V

a-b > +200 mV

space (active)

* Voltage levels at the Receiver

5.8 MODULE 8 - A

NALOG

O

UTPUT

P

ARAMETERS

(

8-Out

)

PARAMETER MENU

0-10

4-20

CALC

HI

b-rEL

LO

b-AbS

tot

A-AbS

A-rEL

NONE

0-20

tYPE

- ANALOG TYPE

asIN

- ANALOG ASSIGNMENT

0.0

to

10.0

sec.

udt

- ANALOG UPDATE TIME

AN-LO

- ANALOG LOW SCALE VALUE

-19999

to

99999

-19999

to

99999

aN-HI

- ANALOG HIGH SCALE VALUE

Advertising