3.3.6 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Ge-
nerally, outputs
OuT.1... OuT.3 can be used each for alarm signalling. If more
than one signal is linked to one output the signals are OR linked. Each of the 3 li-
mit values
Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which
can be switched off individually (parameter = “
OFF”). Switching difference
HYS.x of each limit value is adjustable.
normally closed (
ConF / Out.x / O.Act = 0 )
normally open
(
ConF / Out.x / O.Act = 1 )