10 technical data 42, Technical data 42, 10 technical data – West Control Solutions D280-1 User Manual

Page 42: Technical data, Inputs process value input inp1, Control input di1, Control inputs di2, di3 (option), Filter, Outputs, Relay outputs out1, out2

Advertising
background image

10

Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 15 bits

Decimal point:

0 to 4 digits behind the decimal

point

Limiting frequency: 2 Hz (analog)
Dig. input filter:

adjustable 0,1...100 s

Scanning cycle:

100 ms

Measured value

correction:

2-point or offfset correction

Thermocouple

® Table 1

Input resistance:

‡ 1 MW

Source resistance effect:

1

mV/W

Temperature compensation
Internal temperature compensation

Maximum additional error

± 0,5 K

External temperature compensation

between 0 and 100 °C or adjustable 32 und 212 °F

Break monitoring

Sensor current:

£ 1 mA

Resistance thermometer

® Table 2

Connection technique:

3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitoring:

break and short circuit

Resistance measuring range
The BlueControl software can be used for adaptation of the
characteristic stored for temperature sensor KTY 11-6.

Physical measuring range:

0...450 Ohm
0...4500 Ohm

Number of linearization segments

15

Current and voltage measuring ranges

® Table 3

Span start, span end:

anywhere within the measuring
range

Scaling:

selectable -19999...99999

Linearization:

15 segments, adaptable via
BlueControl

Decimal point:

adjustable

Input circuit monitoring:

with 4..20mA and 2..10V:
12,5% below span start (2mA,
1V)

CONTROL INPUT DI1

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

2,5 V

Current:

50 mA

CONTROL INPUTS DI2, DI3 (OPTION)

Configurable as switch or push-button!
Optocoupler input for active triggering

Nominal voltage

24 V DC external

Current sink (IEC 1131 type 1)
Logic “0”

-3...5 V

Logic “1”

15...30 V

Current requirement

approx.. 5 mA

Transmitter supply U

T

(Option)

Power:

22 mA / ‡ 18 V

If the universal output OUT3 is used there may
be no external galvanic connection between
measuring and output circuits!

FILTER

A first order mathematic filter which is adjustable for time
constant and bandwidth is built in.
The bandwidth is the adjustable tolerance around the process
value within which the filter is active. Measured value changes
exceeding the adjusted bandwidth are output directly.

OUTPUTS

Survey of outputs

Output

Used as

OUT1 (relay)
OUT2 (relay)
OUT3 (logic)

Limit contacts, alarms, control output

OUT3 (continuous)

Control output, process value, set-point,

control deviation,

13V/22mA transmitter power supply

* All logic signals can be combined in an OR function!

RELAY OUTPUTS OUT1, OUT2

Contact type:

2 NO contacts with common
connection

Max. contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

6V, 1 mA DC

Operating life (electr.):

800.000 duty cycles with max.
rating

Note:

If the relays OUT1...OUT3 operate external contactors, these
must be fitted with RC snubber circuits to manufacturer
specifications to prevent excessive switch-off voltage peaks..

Technical data

42

Digital 280-1

Advertising