4 examples for self-tuning attempts 19, Controller – West Control Solutions D280-1 User Manual

Page 19

Advertising
background image

Error-Status Selfoptimization

4.3.3 Acknowledgement procedures in case of unsuccessful self-tuning

1. Press keys Ù and È simultaneously:

The controller continues controlling using the old parameters
The Err LED continues blinking, until the self-tuning error was
acknowledged in the error list.

2. Press key Ù :

Display of error list at extended operating level. After acknowledgement
of the error message, the controller continues control using the old
parameters.

4.3.4 Examples for self-tuning attempts
4.3.5
(controller inverse, heating or heating/cooling)

Start: heating power switched on
Heating power Y is switched off (1).
When the change of process value X
was constant during one minute (2),
the power is switched on (3).
At the reversal point, the self-tuning at-
tempt is finished and the new parameter
are used for controlling to set-point W.

Controller

Digital 280-1

Self-tuning

19

t

2

100%

Y

0%

X

W

start r

1

3

t turning point

blinks

lit

off

Error status

Description

Behaviour

0

No error

3

Faulty control action

Re-configure controller (inverse i direct)

4

No response of process variable The control loop is perhaps not closed: check

sensor, connections and process

5

Low reversal point

Increase ( ADA.H) max. output limiting Y.Hi or

decrease ( ADA.C) min. output limiting Y.Lo

6

Danger of exceeded set-point

(parameter determined)

If necessary, increase (inverse) or reduce (direct)

set-point

7

Output step change too small

(dy > 5%)

Increase ( ADA.H) max. output limiting Y.Hi or

reduce ( ADA.C) min. output limiting Y.Lo

8

Set-point reserve too small

Increase set-point (inverse), reduce set-point

(direct) or increase set-point range(r PArA / SEtp

/ SP.LO and SP.Hi )