7
Calibration level
g
Measured value correction (
CAL)
is only visible if
ConF / InP.1 / Corr = 1
or
2 is chosen.
The measured value can be matched in the calibration menu (
CAL). Two me-
thods are available:
7.1 Offset correction
(
ConF/ InP.1 / Corr =1 ):
possible on-line at the process
2-point correction
(
ConF/ InP.1 / Corr = 2 ):
w is possible off-line with process
value simulator
w online in 2 Schritten zunächst
den einen Wert korrigieren und
später, z.B. nach dem Aufheizen
des Ofens, den zweiten Wert
korrigieren.
Calibration level
Digital 280-1
Offset correction
37
X
standard-setting
Offset-correction
InL
OuL
new
display
OuL
old
X
Standardeinstellung
2-Punkt-Korrektur
InL
InH
OuL
neu
OuH
neu
Display
OuH
alt
OuL
alt