7 calibration level 37, 1 offset correction 37, Point correction 37 – West Control Solutions D280-1 User Manual

Page 37: Calibration (cal) 37, Calibration level (cal) 37 - 39, Offset correction 37 - 39, 7calibration level, Cal), 1 offset correction, Calibration level

Advertising
background image

7

Calibration level

g

Measured value correction (

CAL)

is only visible if

ConF / InP.1 / Corr = 1

or

2 is chosen.

The measured value can be matched in the calibration menu (

CAL). Two me-

thods are available:

7.1 Offset correction

(

ConF/ InP.1 / Corr =1 ):

possible on-line at the process

2-point correction

(

ConF/ InP.1 / Corr = 2 ):

w is possible off-line with process

value simulator

w online in 2 Schritten zunächst

den einen Wert korrigieren und
später, z.B. nach dem Aufheizen
des Ofens, den zweiten Wert
korrigieren.

Calibration level

Digital 280-1

Offset correction

37

X

standard-setting

Offset-correction

InL

OuL

new

display

OuL

old

X

Standardeinstellung

2-Punkt-Korrektur

InL

InH

OuL

neu

OuH

neu

Display

OuH

alt

OuL

alt

Advertising