Parameter adjustment effects, Formulas, Operation – West Control Solutions KS 40-1 Burner User Manual

Page 12

Advertising
background image

Values T

g

and x

max

(step change from 0 to 100 %) or

Dt and Dx (partial step re-

sponse) can be used to determine the maximum rate of increase v

max

.

y =correcting variable

Y

h

=

control range

Tu

=

delay time (s)

Tg

=

recovery time (s)

X

max

=

maximum process value

V

max

=

Xmax

Tg

=

{

{

x

t

= max. rate of increase of process value

The control parameters can be determined from the values calculated for delay
time T

u

, maximum rate of increase v

max

, control range X

h

and characteristic K ac-

cording to the formulas given below. Increase Xp, if line-out to the set-point os-
cillates.

Operation

KS40-1 burner

12

Manual tuning

Tu

Tg

t

x

y

100%

0%

t

Yh

Xmax

{X

{t

Parameter adjustment effects

Parameter

Control

Line-out of disturbances

Start-up behaviour

Pb1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle

td1 higher reduced damping

faster response to disturbances faster reduction of duty cycle

lower

increased damping

slower response to disturbances slower reduction of duty cycle

ti1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle

Formulas

K = Vmax * Tu

controller behavior

Pb1 [phy. units]

td1 [s]

ti1 [s]

With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 £ 0,25 * Tu

PID

1,7 * K

2 * Tu

2 * Tu

PD

0,5 * K

Tu

OFF

PI

2,6 * K

OFF

6 * Tu

P

K

OFF

OFF

3-point-stepping

1,7 * K

Tu

2 * Tu