1 input scaling (only visible with quic = off) 26, Input scaling 26, 1 input scaling (only visible with quic = off) – West Control Solutions KS 40-1 Burner User Manual

Page 26: Parameter setting level

Advertising
background image

5.1 Input scaling (only visible with

qUIC = OFF)

When using current or voltage signals as input variables for

InP.1 or InP.2,

scaling of input and display values at parameter setting level is required. Specifi-
cation of the input value for lower and higher scaling point is in the relevant elec-
trical unit (mA/ V).

5.1.1 Input

Inp.1

g

Parameters

InL.1 , OuL.1, InH.1 and OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.

In addition to these settings,

InL.1 and InH.1 can be adjusted in the range

(0...20mA / 0...10V) determined by selection of

S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.1 and OuL.1 and for InH.1 and

OuH.1 must have the same value.

g

Input scaling changes at calibration level (r page 27) are displayed by input
scaling at parameter setting level. After calibration reset (

OFF), the scaling

parameters are reset to default.

5.1.2 Input

InP.2

As input

InP.1, but only S.Typ = 30 adjustable!

Parameter setting level

KS40-1 burner

26

Input scaling (only visible with

qUIC = OFF)

S.tYP

Input signal

InL.1

OuL.1

InH.1

OuH.1

30

(0...20mA)

0 … 20 mA

0

any

20

any

4 … 20 mA

4

any

20

any

40

(0...10V)

0 … 10 V

0

any

10

any

2 … 10 V

2

any

10

any

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x