8 technical data 32, Technical data 32, Current signal measuring range 32 – West Control Solutions KS 40-1 Burner User Manual

Page 32: Resistance thermometer measuring range 32, Thermocouple measuring range 32, Voltage signal measuring range 32, 8technical data

Advertising
background image

8

Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the
decimal point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value
correction:

2-point or offset correction

Thermocouples

r Table 2 (page 58 )

Input resistance:

³ 1 MW

Effect of source resistance:

1

mV/W

Cold-junction compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

£ 1 mA

Configurable output action

Resistance thermometer

r

Table 2 (page 58 )

Connection:

2 or 3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Potentiometric transducer 50-30-50

W

Current and voltage signals

r

Table 3 (page 58 )

Span start, end of span: anywhere within measuring

range

Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable
with BlueControl

Decimal point:

adjustable

Input circuit monitor:

12,5% below span start
(2mA, 1V)

SUPPLEMENTARY INPUT INP2

Resolution:

> 14 bits

Scanning cycle:

100 ms

Accuracy:

< 0,5 %

Current measuring range

Technical data as for INP1

Potentiometer

r

Table 2 (page 58 )

Connection:

3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break

CONTROL INPUT DI2/DI3

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

5 V

Current:

160

mA

TRANSMITTER SUPPLY U

T

(OPTION)

Power:

22 mA /

³ 18 V

GALVANIC ISOLATION

Safety isolation
Function isolation

KS40-1 burner

32

Power supply

connections

Process value input INP1
Supplementary input INP2
Digital inputs di2, 3
Transmitter supply U

T

Relay outputs OUT 1,2
Relay output OUT3