Offset correction (
ConF/ InP.1 / Corr =1 ):
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration,
OuL.1 is equal to InL.1.
The operator can correct the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.
Calibration level
KS40-1 burner
28
r
М
Щ
3 sec.
r
PArA
CAL
r Ù r
InP.1
Ù
r
InL.1
r
r Ù
r
:
OuL.1
r
r Ù
End
r
r Щ
М
И