Level, Out.1 – West Control Solutions Pro-16 User Manual
Page 31
Configuration
level
9499-040-93811 / 59537-1
Page 31 of 88
Pro-16
Lim
Name
Value range
Description
Default
Fnc.1
Fnc.2
Fnc.3
Function of limit 1/2/3
1
0 switched
off
1
measured value monitoring
2
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è-key, or a digital
input ( ->
LOGI/ Err.r
)
Src.1
Src.2
Src.3
Source of Limit 1/2/3
1
0 process
value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal
setpoint) = deviation alarm to internal setpoint
11
Control deviation Xw (=relative alarm) with suppression
after start-up or set-point change without time limit.
HC.AL
Alarm heat current function (INP2)
0
0 switched
off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating
0
0
switched off / inactive
1
LOOP alarm active. A loop alarm is output, unless the process value
reacts accordingly after elapse of 2 xti1 with Y=100%.
With ti1=0 , the LOOP alarm is inactive!
Hour
OFF..999999 Operating hours (only visible with BlueControl
®
!)
OFF
Swit
OFF..999999 Output switching cycles (only visible with BlueControl
®
!)
OFF
Out.1
Name
Value range Description
Default
O.tYP
Signal type selection OUT1
0
0
relay / logic (only visible with current/logic voltage)
1
0 ... 20 mA continuous (only visible with current/logic/voltage)
2
4 ... 20 mA continuous (only visible with current/logic/voltage)
3
0...10 V continuous (only visible with current/logic/voltage)