Level, Out.1 – West Control Solutions Pro-16 User Manual

Page 31

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 31 of 88

Pro-16

Lim

Name

Value range

Description

Default

Fnc.1
Fnc.2
Fnc.3

Function of limit 1/2/3

1

0 switched

off

1

measured value monitoring

2

Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,

è-key, or a digital

input ( ->

LOGI/ Err.r

)

Src.1
Src.2
Src.3

Source of Limit 1/2/3

1

0 process

value

1

control deviation xw (process value - set-point)

2

control deviation xw (with suppression after start-up and
set-point change)

6

effective setpoint Weff

7

correcting variable y (controller output)

8

control variable deviation xw (actual value - internal
setpoint) = deviation alarm to internal setpoint

11

Control deviation Xw (=relative alarm) with suppression
after start-up or set-point change without time limit.

HC.AL

Alarm heat current function (INP2)

0

0 switched

off

1

Overload short circuit monitoring

2

Break and short circuit monitoring

LP.AL

Monitoring of control loop interruption for heating

0

0

switched off / inactive

1

LOOP alarm active. A loop alarm is output, unless the process value
reacts accordingly after elapse of 2 xti1 with Y=100%.
With ti1=0 , the LOOP alarm is inactive!

Hour

OFF..999999 Operating hours (only visible with BlueControl

®

!)

OFF

Swit

OFF..999999 Output switching cycles (only visible with BlueControl

®

!)

OFF


Out.1

Name

Value range Description

Default

O.tYP

Signal type selection OUT1

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with current/logic/voltage)

2

4 ... 20 mA continuous (only visible with current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)