Figure 2-14, Figure 2-15 – West Control Solutions MRC 8000 User Manual

Page 19

Advertising
background image

19

FIGURE 2-14

Transmitter Power Supply Input
If the isolated 24 VDC regulated transmitter power supply has been specified, the connections
should be made as shown. Connections are made using TB3, terminal 1 is positive and
terminal 2 is negative. The power supply is capable of providing the power needed by up to 2
transducers (40 mADC maximum).

FIGURE 2-15

Position Proportioning Control Output
Position Proportioning control requires that two relays (or SSR Drivers) and the Position
Proportioning Auxiliary input be specified. On a dual pen instrument, either pen may be
configured with Position Proportioning control provided the outputs and auxiliary inputs have
been properly specified.

SHIELDED

TWISTED

PAIRS

1 2

3 4

5

+

-

TB4 or TB5

TB3

1 2

+ -

+ -

1 2

3 4

5

+

-

TB4

TB3

1 2

+ -

1 2

3 4

5

+

-

TB5

+ -

+ -

TWO WIRE

TRANSMITTERS

TWO WIRE

TRANSMITTERS

TWO WIRE

TRANSMITTERS

Modulating Motor

Slidewire
Feedback
Resistance
min. 135
ohms
max. 10K
ohms

L1

L2

OPEN

CLOSE

L

H

C

3

4

5

TB4
or
TB5

1

2

3

4

TB6 or
TB7