Power requirements, Construction, Evironmental and operating conditions – West Control Solutions MRC 8000 User Manual

Page 72: Digital communicatons, General reference data, Approvals and compliance

Advertising
background image

72

POWER REQUIREMENTS

Line Voltage

115/230 VAC,

±

10%, 50/60 Hz

Power Consumption:

25 VA Maximum

CONSTRUCTION

Enclosure

Gasketed cover, case, and windows. Structural foam case and coved with plastic
or glass window area. Door lock available

NEMA Rating

NEMA 3 standard, NEMA 4X optional

Conduit Openings

Four openings standard, 2 additional as required

Mounting

Panel or wall or optional pipe mounting

Overall Dimensions

14.12" wide X 16.77" high X 7.75" deep
(358.65mm wide X 425.96mm high X 196.85mm deep)

Panel Cutout

12.7" wide X 12.7" high
(322.58mm X 322.58mm)

Panel Depth

5.25" (133.35mm)

Panel Protrusion

2.5" (63.5mm)

Weight

20lbs maximum

EVIRONMENTAL AND OPERATING CONDITIONS

Operating Temperature

0

°

C to 55

°

C (32

°

F to 131

°

F)

Storage Temperature

-40

°

C to 65

°

C (-4

°

F to 149

°

F)

Humidity

10 to 90% RH, non-condensing

Vibration

0.5 to 100 Hz @ 0.2g

Mounting Position

Up to 30

°

forward or backward tilt from vertical

Up to 10

°

side tilt from vertical

DIGITAL COMMUNICATONS

Communications Port

RS-485 serial communications, Half-duplex

Protocol

Partlow ASCII - ANSI x 3.28, subcatagory 2.5 & A4

Bit Rate

9600, 4800, 2400, 1200, 600, 300 bits per second

Configuration

Monitor: read only, Normal: read and write

Address

User configurable - 0 to 99 for each pen

GENERAL REFERENCE DATA

Data Backup

Battery backed SRAM for all data

Battery Backup

5 years minimum life, 10 years typically

Warranty

Two years

APPROVALS AND COMPLIANCE

Safety

UL Approved for USA - UL 1092, UL 916, and QUXY - File E67237: Pending
UL Certified for Canada - CSA Spec 142 - File E67237: Pending

Advertising