8 reset to default 31, Reset to default, Power on – West Control Solutions TB 45 Temperature Limiter User Manual
Page 31

6.8
Reset to default
In case of faulty configuration, the device can be
reset to the default manufacturers condition.
1
For this, the operator must keep the keys
increment and decrement pressed during
power-on.
2
Then, press key increment to select
YES
.
3
Press enter to call up the password menu and
to enter the valid password. If the password
is faulty, reset is not possible.
4
Confirm factory resetting with Enter and the
copy procedure is started
(display
COPY
).
5
Afterwards the device restarts.
In all other cases, no reset will occur (timeout
abortion).
g
If one of the operating levels was blocked in BlueControl
Ò
, reset to factory setting is not possible.
g
The copy procedure (
COPY
) can take some seconds.
Now, the transmitter is in normal operation.