Di.fn, Err.r, Baud – West Control Solutions TB 45 Temperature Limiter User Manual

Page 36: Addr, Prty, Dely, S.if

Advertising
background image

Signal allocation LOGI

Name

Value range Description

di.Fn

Function of inputs

0

Direct

1

Inverse

2

Toggle key function (adjustable for 2-point operation with interface and di1)

L_r

Local / Remote switch-over
(Remote: Adjustment of values via front is blocked)

0

no function ( switching via interface is possible)

1

always on

2

di1 switches

7

limit 1 switches

8

limit 2 switches

9

limit 3 switches

Err.r

Source of control signal for resetting all stored error list entries. All error messages
and alarms are in the error list. If an alarm is still pending, i.e. unless the error cause
was removed, stored alarms cannot be acknowledged, i.e. reset. Resetting of all sto-
red error list entries.

2

di1 switches

6

Reset keys switch

Miscellaneous othr

Name

Value range Description

bAud

Baudrate of interface

µ

0

2400 Baud

1

4800 Baud

2

9600 Baud

3

19200 Baud

4

38400 Baud

Addr

1...247

Address

µ

PrtY

Parity

µ

0

No parity, 2 stop bits

1

Even parity

2

Odd parity

3

No parity, 1 stop bit

dELY

0...200

Response delay [ms]

µ

S.IF

Enable system interface µ

0

The system interface is de-activated.

1

The system interface is activated (field bus communication via bus coupler).

Configuration level

36

Configuration

TB 45

Advertising