Galvanic isolation (fig. 1), Power supply, Blueport – West Control Solutions TB 45 Temperature Limiter User Manual

Page 48: Front interface, Bus interface (optional) rs 485, Protocol, System interface

Advertising
background image

Load effect:

ß 0,02%

Resolution:

ß 1,5 úA

Error:

ß 0,1%

Voltage output

0/2...10V, configurable

not continuously short-circuit proof

Control range:

-0,15...11,5 V

Load:

? 2 k[

Load effect:

ß 0,06%

Resolution:

ß 0,75 mV

Error:

ß 0,1%

Additional error with simultaneous
use of current output

ß 0,09%

OUT3astransmittersupply

Output:

22 mA / ? 13 V

OUT3 as logic signal

Load

≤ 700 [

0/ß 23 mA

Load > 500 [

0/> 13 V

GALVANIC ISOLATION (FIG. 1)

Permissible voltages:

Safety isolation:

ß 300 Vrms against earth

Functional isolation:

ß 30 Vrms against earth

POWER SUPPLY

Depending on ordered version:

AC supply

Voltage:

90...250 V AC

Frequency:

48...62 Hz

Power consumption:

approx 9 VA max.

Universal supply 24 V UC

AC voltage:

18...30 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC

Power consumption:

Approx. 3 VA / W max.

Supply only from protective low-voltage sources (SELV)

Behaviour with power failure

Configuration and parameter settings:
Permanent storage in EEPROM

BLUEPORT

®

FRONT INTERFACE

Connection to the transmitter front via a PC adapter (see
‘Accessories’). The BlueControl

®

software enables the TB 45 to be

configured, parameters set, and operated.

BUS INTERFACE (OPTIONAL)

RS 485

Connection via bus connector fitted in the top-hat rail. Screened
cables should be used.

Galvanically isolated
Type:

RS 485

Transmission speed:

2400, 4800, 9600,
19.200, 38.400 bits/s

Parity:

even, uneven, none

Address range:

1...247

Number of devices per bus segment:

32

PROTOCOL

• Modbus RTU

SYSTEM INTERFACE

For connection to field bus coupler (s. System components)
Connection via bus connector in the top-hat rail.

Technical data

48

TB 45

Safety isolation
Function isolation

Power

Relay LC

Input 1

Input 2

di 1 (contact)

di 1 (option

optocoupler)

Output 3

RS 485

System

Relay 2

Front interface

Fig.1: galvanic isolation

Advertising