Multi-Temperature-Controller KS 800

6

Outputs

(For the complete connecting diagram, see section 7.2, 7.3)

6.1

Controller outputs:

Dependent of controller configuration, various output functions are possible:

2-pnt. controller

signaller

1 output

1

)

3-pnt. controller

signaller

2 outputs

2

)

3-pnt. stepping

controller

OUT 1

heating (contr. 1)

heating (contr. 1)

open (contr. 1)

OUT 2

heating (contr. 2)

heating (contr. 2)

open (contr. 2)

OUT 3

heating (contr. 3)

heating (contr. 3)

open (contr. 3)

OUT 4

heating (contr. 4)

heating (contr. 4)

open (contr. 4)

OUT 5

heating (contr. 5)

heating (contr. 5)

open (contr. 5)

OUT 6

heating (contr. 6)

heating (contr. 6)

open (contr. 6)

OUT 7

heating (contr. 7)

heating (contr. 7)

open (contr. 7)

OUT 8

heating (contr. 8)

heating (contr. 8)

open (contr. 8)

OUT 9

switched off

cooling (contr. 1)

closed (contr. 1)

OUT 10

switched off

cooling (contr. 2)

closed (contr. 2)

OUT 11

switched off

cooling (contr. 3)

closed (contr. 3)

OUT 12

switched off

cooling (contr. 4)

closed (contr. 4)

IN/OUT 13

input or unused

cooling (contr. 5)

closed (contr. 5)

IN/OUT 14

input or unused

cooling (contr. 6)

closed (contr. 6)

IN/OUT 15

input or unused

cooling (contr. 7)

closed (contr. 7)

IN/OUT 16

input or unused

cooling (contr. 8)

closed (contr. 8)

1

) Outputs OUT1 to OUT8 are the "signal outputs".

2

) Outputs OUT1 to OUT8 are the "signal outputs 1" and the outputs OUT9 to OUT16 are the

"signal outputs 2".

KS 800 has max. 19 outputs with identical specification:

Transistor outputs, + switching (for loads with common minus connection).
Rated output current:< 70 mA, short-circuit proof
Voltage drop with full load:

typ. 0,3 V, max. 1,0 V

OUT1...OUT12

12 fixed logic outputs (controller outputs). The controllers and control-
ler output allocation are fixed. Reconfiguration is not possible.

IN/OUT13...IN/OUT16

4 variable inputs/outputs. They can be configured as controller outputs
(logic outputs) or digital inputs.

9499 040 49111