Examples 3.6.1 – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 18

Advertising
background image

3.5.4

Data read procedure

Start telegram:

Master sends: Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

ID1

Code

FB no. Fct._no. Type

0

0

Controller

replies:

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

Numb. real values

1)

Numb. integer values

1)

Data telegrams:

Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2 Byte 3

Byte 4 - 7

0x68 count

0x68 count

Value

Thereby, the first value is sent with Count = 1. For flow control, count is reflected by KS800 (? once). The

values are transmitted in the order real - integer.
End telegram:

Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2-3

Byte 4 - 7

0x16

0x16

Result

3.6

Examples

3.6.1

Function block protocol principles

A function block has input and output data (process data) as well as parameter and configuration data. It is

addressable via a function block number.
The following access mechanisms are used:

3.6.2

Individual access

This access (code xx) can be used for reading or writing an individual value of a function.

Valid values for ID1:

Configuration as

FixPoint:

0 = integer

real values are transmitted as integer (without digits behind the decimal point)

1 = real

real values are transmitted as FixPoint (1 digit behind the decimal point)

Example 1:

(message structure with data sending)

Transmission of parameter set number (ParNr = 1) to the controller (channel 2).

Start telegram:

Master sends: Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

0

31

52

5

0

0

1

Controller

replies:

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

0x10

Data telegrams:

Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2 Byte 3

Byte 4 - 7

0x68

1

1

0x68

1

End telegram:

Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1

Byte 2 - 3

Byte 4 - 7

0x16

0x16

0

Process data

9499 040 50511

18

1) If a Read Service was refused, these values = 0