Code tables 5.2.1 – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 27

Advertising
background image

5.2

CODE tables

5.2.1

Structure of configuration words (C.xxxx)

The configuration words given in the following code tables comprise several partial components, which can

be transmitted only in common.

The data in the table must be interpreted as follows:

Example (C100): Code Descr. R/W Type Description

Range

71

C100 R/W INT

CFunc: Controller function

WFunc:Set-point function

(T,H)

(E)

0..xx0z

Description

CFunc

WFunc

Thousands Hundreds

Ones

Range

x

x

z

00 ... 07

0...1

Example: 2-pnt. controller;

Set-point / cascade

0 2 0 4

g

- For transmission of configuration words, see chapter page 19.

- The possible settings of the configuration words are given in the KS800

function description (order no.: 9499 040 49218)

5.2.2

INSTRUMENT (FB no.: 0 type no.: 0)

All data which are valid for the overall instrument are grouped in function block ‘INSTRUMENT’.

Process data

General

(Function no.: 0)

Code Descr.

R/W Type Description

Range

Rem.

01

Unit_State 1

R

ST1

Status 1

A

10

Block 13..15, 18

R

Block

13

Write Error

R

INT

Error during last write access

0, 100...127

14

Write Error

Position

R

INT

Position of last write access error

0...99

15

Read Error

R

INT

Error during last read access

0, 100...127

16

DPErr

R

ICMP Error messages from DP module

B

17

DPAdr_eff

R

INT

Effective PROFIBUS address

0...126

18

Type

R

INT

Type no. of function block

0

20

Block 21...27

R

Block

21

HWbas

R

INT

Basic HW options: module A, P

C

23

SWopt

R

INT

SW options 1

D

24

SWcod

R

INT

SW code no. 7th-10th digit of 12NC

wxyz

E

25

SWvers

R

INT

SW code no. 11th-12th digit of 12NC

00xy

F

26

OPVers

1)

R

INT

Operating version

27

EEPVers

1)

R

INT

EEPROM version

31

OpMod

R/W INT

Instrument switch-over to configuration mode (only after 1) 0

Instrument switch-over to online mode (only after 0)

1

Cancellation of configuration mode (only after 0)

2

32

Ostartg

R/W INT

Stop/start self-tuning for all group controllers

0..1

33

UPD

R/W INT

Acknowledgement of local data change

0..1

G

34

HC_reset

R/W INT

Heating-current-reset / Quicktest

0...3

G2

27

9499 040 50511

Function block protocol

1) Data are reserved for distinction of internal versions in future applications.

Advertising