6function modules 6.1, Function module for simatic, Structure – West Control Solutions KS 800 Profibus Interface Manual User Manual

Page 43: Function modules

Advertising
background image

6

Function modules

6.1

Function module for SIMATIC

®

S5

Function module FB206 serves for easy access to the controller parameter and configuration data (in P area).

6.1.1

Structure

The parameters of the function module are:

Name

Type Description / function

A-A

KF Start of output bytes for send window

E-A

KF Start of input bytes for receive window

DB-S

B

Data module for parameter data

DWAS

W Data word start for order in DB

DWLR

W Number of real values

DWLI

W Number of integer values

DWLC

W d.c. always ‘0’

SERV

W Service (read/write)

CODE

W Code

FBNR

W Function block no.

FKNR

W Function no.

TYP

W d.c. (always ‘0’)

TIME

KH Timeout in time units, decremented with each FB call, must be higher than timeout in DP module.

ANZW

W

The current transmission status for the selected data area is given in the display word. The structure of

the display word is:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Timeout

(FB)

Service

faulty

NAK

(access

by

controller

not

accepted)

Parity

error

Timeout

internal

(controller)

Wait

for

end

telegram

Service

(0=Read;

1=Write)

Reset

order

Waits

for

acknowledgement

Order

ready

with

error

O<%-2>rder

ready

without

error

Order

running

The function module reads or writes KS800 parameter/configuration data.

w

A-A, E-A

The input addresses or output addresses of the parameter channel are

entered into these parameters. The addresses are determined during

configuration of the unit connected to the PROFIBUS (Ä Fig.:

S.23)

w

DB-S

DB-S is used for allocation of the data module pertaining to the

function module, in which all FB operations are handled. It must have

been opened previously.

Data words 0...3 of the data module are “provisional markers”, which

are enabled again after FB handling.

w

DWAS

DWAS identifies the start of the data area in the data module. The first 4 words after DWAS are

required for internal use in the function module and must not be used for other purposes.Example: 2

data sets shall be stored with high packing density in DB25.

Function modules

43

9499 040 50511

FB206

A-A

E-A

DB-S

DWAS

DWLR

DWLI

DWLC

SERV

CODE

FBNR
FKNR

TYP

TIME

ANZW

DBxx

...
...

Byte 11

E-Adr.

P000
P002
P004
P006
P007
P008

...

A-Adr.

P000
P002
P004
P006

...