ULTIMA WATER COOLED

Chillers

12

Chillers

Technical Manual : Part No 6259477 V1.4.0_07_2014

Design Features & Information

MINIMUM SYSTEM WATER VOLUME CALCULATIONS

METHOD 1

Where the system permanent heat load is known:

Vm =

Water Flow Rate (litres/minute) x Minimum Compressor Run Time
(mins) x Chiller Loading Factor

Where

Vm is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes

Chiller Loading Factor =

Minimum Turndown (kW) x 1.2

Permanent Heat Load

The Chiller Loading Factor limits:
Max

1.00

Min

0.25

Example 250 kW Chiller, 7/12°C Water, Model UWC250DQ with a permanent load of 95 kW

litres

1085

95

1.2

60

2

5

4.19

60

250

Vm

METHOD 2

Where the system permanent heat load is unknown:

Vm =

Water Flow Rate (litres/hour) x Minimum Turndown Ratio x 1.2

Maximum Compressor Starts Per Hour

Where

Minimum Turndown Ratio = Minimum Stage Capacity (kW)

Chiller Full Capacity (kW)

Example

250 kW Chiller, 7/12°C Water, Model UWC250DQ permanent load unknown.

litres

1031

12

1

x

1.2

x

250

60

x

5

x

4.19

3600

x

250

Vm

Method 1 is always preferred.