Installation Data

POSITIONING

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly.

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections.

Observe airflow and maintenance clearances.

Pipework and electrical connections are readily accessible.

Where multiple units are installed, due care should be taken to avoid the
discharge air from each unit adversely affecting other units in the vicinity.

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.


C

A

500

500

Controls

Panel

Inlet /
Outlet

B

Model Size

A

B

C

UWC 75

– 125

mm

1800

760

760

UWC 150

– 250 (Ex. 240)

mm

2000

760

760

UWC 240

– 450 (Ex. 250)

mm

3200

900

900