Electrical data, Ultima water cooled chillers, General specification – Airedale Ultima Water Cooled 75kW - 450kW User Manual

Page 26

Advertising
background image

ULTIMA WATER COOLED

Chillers

26

Chillers

Technical Manual : Part No 6259477 V1.4.0_07_2014

General Specification

ELECTRICAL DATA

UWC75

UWC100

UWC125

UWC150

UWC175

Unit Data

Nominal Run Amps

(1)

A

46

57

65

80

90

Maximum Start Amps

(2)

A

134

170

216

258

290

Permanent Supply

VAC

230V 1PH 50Hz

Mains Supply

VAC

400V 3PH 50Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Rec Mains Fuse Size

A

63

80

100

125

125

Max Permanent Incoming Cable
Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

70 (direct to MCCB)

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

40

40

40

80

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Compressor - Per Compressor

Quantity

4

4

4

4

2+2

Motor Rating

kW

5.3

7.3

9.1

10.9

10.9/14.4

Nominal Run Amps

(1)

A

11.5

14.2

16.3

20.0

20.0/25.2

Crankcase Heater Rating

W

70.0

70.0

70.0

70.0

70.0/120.0

Start Amps

(2)

99

127

167

198

198/225

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1)

A

41

51

58

72

81

Maximum Start Amps

(2)

A

130

165

211

252

283

Recommended Mains Fuse

A

63

80

100

100

125

Compressor Nominal Run
Amps - Per Compressor

A

10.3

12.7

14.6

17.9

17.9/22.5

Electronic Soft-Start

Nominal Run Amps

(1)

A

46

57

65

80

90

Maximum Start Amps

(2)

A

90

119

149

179

200

Recommended Mains Fuse

A

63

80

100

125

125

(1)

Based at 12/7°C evaporator water and 30/35°C condenser water.

(2)

Starting amps refers to the direct on line connections.