Chillers

ULTIMA WATER COOLED

Chillers

39

Technical Manual : Part No 6259477 V1.4.0_07_2014

Dry Cooler Specification

GENERAL SPECIFICATION

Water Cooled Chiller

UWC300

UWC330

UWC360

UWC400

UWC450

Matched Dry Cooler

– Per Unit

DE300 x 2

DE300 & DE360

DE360 x 2

DE360 & DE450

DE450 x 2

Sound Data

Sound Pressure Level at 10m

dB(A)

57

57 & 59

59

59 & 59

59

Mechanical Data

Dimensions

Horizontal - H x L x W -

mm

1383 X 6228 X 795

1383 X 6228 X 795

&

2436 X 4783 X 878

2436 X 4783 X 878

2436 X 4783 X 878

&

2436 X 4783 X 878

2436 X 4783 X 878

Vertical

– H x L x W

mm

1335 X 6228 X 1272

1335 X 6228 X 1272

&

1335 X 4783 X 2436

1335 X 4783 X 2436

1335 X 4783 X 2436

&

1335 X 4783 X 2436

1335 X 4783 X 2436

Weight - Machine

kg

611

611 & 860

860

860 & 860

860

Construction - Material / Colour

Painted Galvanised Steel

– Light Grey (RAL 9002)

Dry Cooler Coil

Nominal Airflow

m³/s

21.7

21.7 & 21.7

32.0

32.0 & 32.0

32.0

Discharge

Vertical or Horizontal

Fan & Motor

Quantity

4

4 & 6

6

6 & 6

6

Diameter

mm

800

800 & 800

800

800 & 800

800

Maximum Speed

rpm

890

890 & 890

890

890 & 890

890

Connections

Water Inlet / Outlet

in

3

3 & 4

4

4 & 4

4

Electrical Data

Mains Supply

VAC

400V 3PH 50Hz

Nominal Run Amps

A

16.0

16.0 & 24.0

24.0

24.0 & 24.0

24.0

(1)

Standard unit match based on 12/7°C chilled water, 40/45°C condenser glycol solution (20% ethylene), 30° ambient. For alternative
conditions, please contact Airedale.

WATERSIDE PRESSURE
DROPS

CH

IL

LER PRESSU

RE DR

O

P

(k

Pa

)

0

20

40

60

80

100

120

140

160

180

200

2

4

6

8

10

12

14

16

18

20

22

24

26

28

DE75

DE100

DE125

DE150

DE175

DE200 DE225/360/

450

DE250

DE240

DE300

WATERFLOW (l/s)

(1)

For glycol solutions, please refer to

Glycol Data

.

Advertising