Sound data, Chillers ultima water cooled, Performance data – Airedale Ultima Water Cooled 75kW - 450kW User Manual

Page 21: Chillers, Measurement of sound data, Global chiller sound level

Advertising
background image

Chillers

ULTIMA WATER COOLED

Chillers

21

Technical Manual : Part No 6259477 V1.4.0_07_2014

Performance Data

SOUND DATA

Measurement of Sound
Data

All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1 : 1995. The Global sound data quoted is valid for sound
emitted in the horizontal plane in all directions

All Sound Power Levels quoted are calculated from measured sound intensity according
to BS EN ISO9614 Part 1 : 1995.

Sound Pressure Levels are calculated from sound power using the expanded
parallelepiped method according to BS EN ISO11203 : 1996.

Global Chiller Sound Level

Standard - D Models

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UWC75D

Power

84

71

50

69

81

78

79

76

Pressure

@ 10m

53

39

19

37

49

46

47

44

UWC100D

Power

83

75

48

63

79

76

77

74

Pressure

@ 10m

51

43

16

32

47

45

46

42

UWC125D

Power

85

78

53

66

78

76

81

79

Pressure

@ 10m

54

47

21

34

46

44

49

47

UWC150D

Power

85

84

55

71

80

77

81

75

Pressure

@ 10m

53

53

23

39

48

46

49

44

UWC175D

Power

87

82

54

70

78

82

83

77

Pressure

@ 10m

55

51

23

38

47

50

51

45

UWC200D

Power

88

78

53

69

75

84

84

78

Pressure

@ 10m

57

46

21

38

44

52

53

46

UWC225D

Power

92

77

55

74

81

88

88

81

Pressure

@ 10m

61

45

23

42

49

56

57

49

UWC240D

Power

90

96

90

89

90

80

82

77

Pressure

@ 10m

62

68

62

61

62

52

54

49

UWC250D

Power

94

75

56

76

83

90

90

83

Pressure

@ 10m

63

43

25

45

52

58

59

51

UWC270D

Power

91

94

89

89

89

85

84

79

Pressure

@ 10m

63

66

61

61

61

57

56

51

UWC300D

Power

91

90

88

88

86

87

85

80

Pressure

@ 10m

63

62

60

60

58

59

57

52

UWC330D

Power

95

88

90

93

91

91

90

83

Pressure

@ 10m

67

60

62

65

63

63

62

55

UWC360D

Power

98

86

91

95

94

93

92

84

Pressure

@ 10m

70

58

63

67

66

65

64

56

UWC400D

Power

98

87

92

96

95

93

92

85

Pressure

@ 10m

70

59

64

68

67

65

64

57

UWC450D

Power

99

88

93

96

95

94

93

86

Pressure

@ 10m

71

60

65

68

67

66

65

58

1

dB(A) is the overall sound level, measured on the A scale.
All performance data is supplied in accordance with BS EN 14511-1:2013

2

All sound data measured at nominal conditions: Based at 12/7°C evaporator water and 30/35°C condenser water.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment
is placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.