Performance data, Capacity data, Ultima water cooled chillers – Airedale Ultima Water Cooled 75kW - 450kW User Manual

Page 16: Chillers

Advertising
background image

ULTIMA WATER COOLED

Chillers

16

Chillers

Technical Manual : Part No 6259477 V1.4.0_07_2014

Performance Data

All performance data is supplied in accordance with BS EN 14511-1:2013

CAPACITY DATA

Condenser Leaving/Entering Water Temperature

– based on

T of 5°C

Leaving Water

Temperature °C

25/30°C

30/35°C

35/40°C

40/45°C

Output kW

Input kW

Output kW

Input kW

Output kW

Input kW

Output kW

Input kW

UWC75

5

85.6

19.2

81.6

21.6

77.5

24.1

73.3

26.7

6

88.7

19.3

84.6

21.7

80.3

24.2

76.0

26.7

7

91.7

19.6

87.5

22.0

83.1

24.5

78.7

27.0

10

101.7

20.1

97.0

22.4

92.3

24.8

87.5

27.2

UWC100

5

116.4

25.5

111.3

28.9

105.9

32.3

100.6

35.9

6

120.6

25.6

115.2

29.0

109.7

32.5

104.2

36.0

7

124.5

25.9

118.9

29.3

113.3

32.8

107.6

36.3

10

137.1

26.3

131.1

29.8

125.0

33.2

118.9

36.7

UWC125

5

148.5

32.8

141.8

36.8

134.9

41.0

127.9

45.3

6

153.8

33.0

146.9

37.0

139.7

41.2

132.5

45.5

7

159.2

33.4

152.0

37.4

144.6

41.6

137.2

45.8

10

176.2

34.0

168.4

37.9

160.2

42.1

152.0

46.3

UWC150

5

180.3

39.3

172.3

44.2

164.1

49.2

155.7

54.4

6

186.5

39.7

178.2

44.5

169.8

49.5

161.1

54.7

7

192.7

40.2

184.2

45.0

175.5

49.9

166.6

55.0

10

212.6

41.4

203.3

46.0

194.0

50.7

184.3

55.6

UWC175

5

208.6

44.4

199.2

50.0

189.7

55.8

179.7

62.0

6

215.9

44.7

206.2

50.2

196.4

56.0

186.1

62.2

7

223.1

45.1

213.1

50.7

202.9

56.5

192.5

62.6

10

246.2

45.9

235.4

51.5

224.5

57.2

213.2

63.3

UWC200

5

237.8

49.9

227.1

56.2

216.0

62.8

204.4

69.8

6

246.3

49.9

235.2

56.2

223.7

62.9

211.8

69.9

7

254.4

50.4

242.9

56.9

231.1

63.6

219.0

70.6

10

281.0

50.6

268.7

57.1

256.1

63.9

243.1

71.1

UWC225

5

268.8

56.7

255.7

63.6

242.3

70.9

228.4

78.5

6

278.4

56.9

264.8

63.9

250.9

71.1

236.6

78.7

7

287.7

57.4

273.7

64.5

259.5

71.7

244.9

79.2

10

317.7

58.3

302.6

65.4

287.3

72.6

271.7

80.1

UWC240

5

257.0

54.8

244.9

62.2

232.4

69.9

219.8

77.8

6

266.1

55.2

253.5

62.5

240.7

70.1

227.7

77.9

7

275.2

55.6

262.2

62.9

249.0

70.4

235.6

78.2

10

303.4

57.0

289.3

64.1

275.1

71.4

260.7

78.8

UWC250

5

300.5

62.0

286.8

69.1

272.2

77.0

256.8

85.6

6

312.3

63.6

296.4

71.1

280.2

78.9

263.5

87.2

7

322.7

64.4

306.3

72.0

289.7

79.8

272.6

87.9

10

356.6

65.7

338.8

73.3

320.8

81.0

302.6

88.9

UWC270

5

300.1

63.1

285.6

71.6

270.8

80.3

255.8

89.3

6

310.6

63.4

295.7

71.9

280.5

80.6

265.0

89.6

7

321.3

63.8

305.9

72.2

290.3

80.9

274.4

89.9

10

354.3

64.8

337.7

73.3

320.9

81.9

303.9

90.8

UWC300

5

345.1

71.3

328.1

81.0

310.8

90.9

293.2

101.0

6

357.2

71.6

339.7

81.2

321.9

91.1

303.8

101.3

7

369.4

71.8

351.4

81.5

333.1

91.5

314.6

101.7

10

407.4

72.4

388.0

82.4

368.5

92.6

348.8

102.9

UWC330

5

389.8

81.0

369.5

91.5

348.9

102.4

327.9

113.6

6

403.6

81.4

382.8

91.9

361.6

102.8

340.0

114.0

7

417.6

81.8

396.1

92.4

374.4

103.2

352.3

114.4

10

461.1

83.0

437.9

93.7

414.6

104.6

391.0

115.7

UWC360

5

435.4

90.8

411.6

102.2

387.6

114.0

363.1

126.2

6

451.0

91.4

426.5

102.7

401.8

114.5

376.6

126.6

7

466.7

92.0

441.6

103.3

416.3

115.0

390.4

127.1

10

515.7

93.8

488.6

105.2

461.4

116.7

433.8

128.6

UWC400

5

477.8

102.1

453.3

115.0

428.7

128.1

403.6

141.7

6

494.8

102.7

469.6

115.5

444.3

128.6

418.4

142.2

7

512.0

103.2

486.0

116.1

460.0

129.2

433.4

142.7

10

565.5

104.8

537.3

117.8

509.3

130.9

480.7

144.4

UWC450

5

518.2

113.3

493.3

127.7

468.4

142.1

442.8

157.1

6

536.6

113.8

510.9

128.1

485.2

142.6

458.8

157.6

7

555.1

114.3

528.6

128.7

502.1

143.2

475.0

158.2

10

612.8

115.6

583.9

130.3

555.3

145.0

526.1

160.0

1

Output kW refers to the chilled water duty.

2

Input kW refers to the compressor input power.

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate

5

Evaporator Water flow rate (l/s) = Output ÷ (4.19 x

T) Except Glycol use, refer to

Glycol Data

.

6

Condenser Water flow rate (l/s) = (Output + Input) ÷ (4.19 x

T) Except Glycol use, refer to

Glycol Data

.

7

For conditions outside those quoted, please refer to Airedale.

Advertising