ULTIMA WATER COOLED

Chillers

24

Chillers

Technical Manual : Part No 6259477 V1.4.0_07_2014

General Specification

MECHANICAL DATA

UWC200

UWC225

UWC240

UWC250

UWC270

Duty

– Cooling

Cooling Only

(1)

kW

242.9

273.7

262.2

306.3

305.9

Nominal Input

(1)

kW

56.9

64.5

62.9

72.0

72.2

EER

(2)

4.3

4.2

4.17

4.3

4.2

Capacity Steps

%

0-25-50-75-100 0-20-30-50-70-80-100 0-17-33-50-67-83-100

0-25-50-75-100 0-19-33-52-67-86-100

Dimensions - H x L x W

mm

1850 x 2000 x 760

1900 x 3200 x 900 1850 x 2000 x 760 1900 x 3200 x 900

Weight

Machine - D

kg

1450

1525

1420

1590

1750

- DQ

kg

1490

1565

1490

1630

1820

- DSQ

kg

1520

1595

1510

1670

1840

Operating - D

kg

1490

1580

1490

1650

1830

- DQ

kg

1530

1620

1560

1690

1900

- DSQ

kg

1560

1650

1580

1730

1920

Construction - Material / Colour

Plain Galvanised Steel Base with Galvanised Sheet Steel, Epoxy Baked Powder Paint

Superstructure

– Light Grey (RAL 7035)

Evaporator

Brazed Plate

Insulation

Class 0

Quantity

1

1

1

1

1

Water Volume

l

14.6

22.1

22.5

24.8

27.0

Total Max. Water Flow

l/s

16.8

19.0

18.1

21.3

21.1

Condenser

Brazed Plate

Insulation

Class 0

Quantity

1

1

2

1

2

Water Volume Circuit 1

l

26.6

31.1

23.9

35.6

23.9

Water Volume Circuit 2

l

N/A

N/A

23.9

N/A

32.9

Total Max. Water Flow

l/s

19.8

22.5

18.1

25.2

21.1

Compressor

Tandem Scroll - Hermetic

Trio Scroll

Hermetic

Tandem Scroll -

Hermetic

Trio Scroll

Hermetic

Quantity

4

4

6

4

6

Oil Charge Volume (Total)

l

4 x 4.7 6.3 + 4.7 + 6.3 + 4.7

6 x 3.4

4 x 6.3

4.7+4.7+4.7+3.4+3.4+3.4

Oil Type

Polyol Ester

Refrigeration

Dual Circuit

Refrigerant Control

Electronic Expansion Valve

Refrigerant Precharged

R407C

Charge (Total)

Kg

15.0 + 15.0

18.6 + 18.6

17.6 + 17.6

20.8 + 20.8

23.2 + 18.7

Connections - Evaporator

Suits

“Victaulic” type Coupling & Pipe Assembly

Water Inlet / Outlet

mm / (in)

65 (2 1/2

”)

80 (3

”)

80 (3

”)

80 (3

”)

80 (3

”)

Connections - Condenser

Suits

“Victaulic” type Coupling & Pipe Assembly

Water Inlet / Outlet

mm / (in)

80 (3

”)

80 (3

”)

80 (3

”)

80 (3

”)

80 (3

”)

Water System - Evaporator

Min. System Water Volume (3)

l

1044

941

763

1317

995

Max. System Press

Bar

10

10

10

10

10

Water System

– Condenser 1

Min. System Water Volume (3)

l

1289

1163

927

1626

1213

Max. System Press

Bar

10

10

10

10

10

Water System

– Condenser 2

Min. System Water Volume (3)

L

N/A

N/A

927

N/A

944

Max. System Press

Bar

N/A

N/A

10

N/A

10

(1)

Nominal Cooling Duties based on 12/7°C evaporator water and 30/35°C condensing water, where output is the chilled water
duty and input is the compressor input power.
All performance data is supplied in accordance with BS EN 14511-1:2013

(2)

EER is the Cooling Duty

compressor input power.

(3)

For minimum system volume refer to

Minimum System Water Volume Calculations

.