Ultima water cooled chillers, Performance data, Chillers – Airedale Ultima Water Cooled 75kW - 450kW User Manual

Page 22: Sound data, Global chiller sound level

Advertising
background image

ULTIMA WATER COOLED

Chillers

22

Chillers

Technical Manual : Part No 6259477 V1.4.0_07_2014

Performance Data

All performance data is supplied in accordance with BS EN 14511-1:2013

SOUND DATA

Global Chiller Sound Level

Quiet - DQ Models

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UWC75DQ

Power

81

67

66

75

77

74

75

72

Pressure

@ 10m

49

35

35

43

45

42

43

40

UWC100DQ

Power

79

71

64

69

75

72

73

70

Pressure

@ 10m

47

39

32

38

43

41

42

38

UWC125DQ

Power

81

74

69

72

74

72

77

75

Pressure

@ 10m

50

43

37

40

42

40

45

43

UWC150DQ

Power

81

80

71

77

76

73

77

71

Pressure

@ 10m

49

49

39

45

44

42

45

40

UWC175DQ

Power

83

78

70

76

74

78

79

73

Pressure

@ 10m

51

47

39

44

43

46

47

41

UWC200DQ

Power

84

74

69

75

71

80

80

74

Pressure

@ 10m

53

42

37

44

40

48

49

42

UWC225DQ

Power

88

73

71

80

77

84

84

77

Pressure

@ 10m

57

41

39

48

45

52

53

45

UWC240DQ

Power

89

95

89

89

90

77

77

71

Pressure

@ 10m

61

67

61

61

62

49

49

43

UWC250DQ

Power

90

71

72

82

79

86

86

79

Pressure

@ 10m

59

39

41

51

48

54

55

47

UWC270DQ

Power

89

93

88

88

88

81

79

72

Pressure

@ 10m

61

65

60

60

60

53

51

44

UWC300DQ

Power

88

89

87

87

86

84

80

74

Pressure

@ 10m

60

61

59

59

58

56

52

46

UWC330DQ

Power

93

88

89

92

91

87

84

77

Pressure

@ 10m

65

60

61

64

63

59

56

49

UWC360DQ

Power

95

86

90

94

94

89

87

78

Pressure

@ 10m

67

58

62

66

66

61

59

50

UWC400DQ

Power

96

86

91

95

95

90

87

79

Pressure

@ 10m

68

58

63

67

67

62

59

51

UWC450DQ

Power

96

87

92

96

95

91

88

80

Pressure

@ 10m

68

59

64

68

67

63

60

52

Super Quiet - DSQ
Models

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UWC75DSQ

Power

80

66

65

74

76

73

74

71

Pressure

@ 10m

48

34

34

42

44

41

42

39

UWC100DSQ

Power

78

70

63

68

74

71

72

69

Pressure

@ 10m

46

38

31

37

42

40

41

37

UWC125DSQ

Power

80

73

68

71

73

71

76

74

Pressure

@ 10m

49

42

36

39

41

39

44

42

UWC150DSQ

Power

80

79

70

76

75

72

76

70

Pressure

@ 10m

48

48

38

44

43

41

44

39

UWC175DSQ

Power

82

77

69

75

73

77

78

72

Pressure

@ 10m

50

46

38

43

42

45

46

40

UWC200DSQ

Power

83

73

68

74

70

79

79

73

Pressure

@ 10m

52

41

36

43

39

47

48

41

UWC225DSQ

Power

87

72

70

79

76

83

83

76

Pressure

@ 10m

56

40

38

47

44

51

52

44

UWC240DSQ

Power

88

94

88

88

90

72

69

63

Pressure

@ 10m

60

66

60

60

62

44

41

35

UWC250DSQ

Power

89

70

71

81

78

85

85

78

Pressure

@ 10m

58

38

40

50

47

53

54

46

UWC270DSQ

Power

87

92

87

87

88

76

72

64

Pressure

@ 10m

59

64

59

59

60

48

44

36

UWC300DSQ

Power

85

88

86

86

85

79

73

65

Pressure

@ 10m

57

60

58

58

57

51

45

37

UWC330DSQ

Power

90

87

88

91

91

82

77

68

Pressure

@ 10m

62

59

60

63

63

54

49

40

UWC360DSQ

Power

92

85

89

93

93

84

79

70

Pressure

@ 10m

64

57

61

65

65

56

51

42

UWC400DSQ

Power

93

85

90

94

94

85

80

71

Pressure

@ 10m

65

57

62

66

66

57

52

43

UWC450DSQ

Power

94

86

91

95

95

86

81

72

Pressure

@ 10m

66

58

63

67

67

58

53

44

1

dB(A) is the overall sound level, measured on the A scale.

2

All sound data measured at nominal conditions: Based at 12/7°C evaporator water and 30/35°C condenser water.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment
is placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.

Advertising