ORION SE Settings Tab Fields

Region

This field is not applicable for Endpoint Settings

Interval

Determines how often the endpoint collects readings—every 15 minutes or every hour

Reading Options

Determines endpoint collection

Collect Current Reads Only*: When the button is selected and the Current Reads schedule

runs, the current read for the endpoint is retrieved

Collect Historical Reads*: When the button is selected and the Historical Reads schedule

runs, historical reads for the endpoint are retrieved

Push Reads: A selected button indicates a push read When a gateway receives data set as a

push read from an endpoint, it does not hold it for the scheduled time The gateway forwards

the data to ReadCenter Analytics automatically when it is received

Alarm Notification

Alarms selected are sent immediately to ReadCenter Analytics when the condition is detected by

the endpoint Check the box next to "Alarm Notification" to activate the check boxes

OTE:

N

Alarms set on the Endpoint Settings screen are reflected on the Account Records screen

OTE:

N

Alarm Notifications are set up during Training, if needed Notifications set on this screen

can result in high backhaul usage charges if there are a large number of accounts

selected To set alarm notifications for single endpoints, refer to

"ORION SE – Fixed Network

Only" on page 60

*

Neither Current Reads Only or Historical Reads affects what is saved by the gateway The gateway always saves historical

reads The settings only impact what is returned for each endpoint when the Current Reads or Historical Reads schedule

runs Refer to

"Defining Gateway Schedules" on page 78

for more information on gateway schedules

Buttons

View Selected

Accounts

View and verify the accounts for which you are changing the settings Accounts are displayed in a

grid format Double-click an individual row or click Show Account if you want to see the account

record details

Apply ORION SE

Settings

Applies the settings to all selected accounts Settings are saved within ReadCenter for the account,

route or group selected A confirmation message displays

Edit

Activates the fields to make changes Selecting Edit brings up a Password window The Password

must be entered to make changes to the endpoint settings

View Endpoints Set

View a report of all the endpoints settings currently defined The information can be written to a

comma-delimited file Double-click an individual row or click Show Account if you need to see

the account record details This feature is primarily used by Badger Meter Technical Support for