Additional ProgrammingE: Industrial Analog and Industrial Pulse (ILR 710 & ILR 730)

Output Pulse Length

(For model ILR 710 only)
Indicated by a “P” on the left-hand side of the display, this screen allows the selection of the low duration of the output pulse

“0” for zero milliseconds (Pulse Output is disabled)

“2” for 2 milliseconds

“10” for 10 milliseconds

“20” for 20 milliseconds

“40” for 40 milliseconds

“100” for 100 milliseconds

To advance to the next programming screen, hold the TOTAL button

PER MIN

Figure 9E: Output Pulse Length Screen

About Output Pulse Length: The pulse rate duration should take into account the "Pulse Rate Out" and maximum meter flow

rate, to prevent an output pulse duration greater than the required time between pulses The Output Pulse Length should be

set to less than the value of “t ”
Per the equation:
Maximum Meter Flow Rate (in gpm or lpm)
t = ----------------------------------------------------------------- x 1000
60X Output Pulse Rate
where t = the required pulse rate in milliseconds
The Output Pulse Rate = the programmed parameter (default = 1 00 ppl/ppg)
The Maximum Meter Flow Rate = the maximum flow rate of the meter for the application