Control system layout, Specifications – Badger Meter Water Conditioning User Manual

Page 14

Advertising
background image

CONTROL SYSTEM LAYOUT

Output Relay Contacts

Remote Control

Panel

Cycle

Controller

Timer

Pump

Audible

Alarm

Treatment

System

Flow Meter

RTR (Disc/RCDL Turbo) or

AR/t (Industrial Turbo)

SPECIFICATIONS

Power Input

85…265V AC, 47…63 Hz

Signal Inputs

Transmitter Pulse Input Dry switch closure or electronic transmitter (current sinking)

Lockout Signal Input Dry switch closure/open collector and 115V AC (optically

isolated)

Remote Start and Stop

Input

Dry switch closure/open collector (optically isolated)

Output Signal

Form C Contact

250V AC / 30V DC @ 0 5 amp, resistive

Operating Modes

Programmable

Manual Reset and start on command only

Automatic Timed output signal and auto reset at end of batch

Programmable Functions

Output Signal Duration 1…9999 seconds (auto mode)

Batch Size Maximum of 99,999,900 gallons, depending on meter size

115V AC Lockout NO or NC programmable

Environmental

Operating Temperature 32…122° F (0…50° C)

Operating Humidity Up to 85% non-condensing

Display

4-line alphanumeric, LCD

Model PRC-20 with AR/t or RTR® Water Conditioning Control System

Page 14