Transmitter input, Regeneration relay output, Common normally closed normally open – Badger Meter Water Conditioning User Manual
Page 8
Advertising
Transmitter Input
12V 15 16 17
Gnd
AR/t
Pulse Transmitter
- black
+ white
RTR
Transmitter Register
- black
+ red
12V 15 16 17
Gnd
Reed
Switch
black
black
12V 15 16 17
Gnd
Regeneration Relay Output
1 2 3
Common
Normally closed
Normally open
5A, 250 VAC / 30 VDC max.
12-24 AWG
Suppress inductive loads with
RC surge suppressor (150
ohm, 0.25 microfarad, 600 V)
Model PRC-20 with AR/t or RTR® Water Conditioning Control System