OPERATION

The basic function of the Badger Meter

®

PRC-20 controller is to provide a relay output signal to external equipment to control

tank regeneration Regeneration may be started automatically when a predetermined amount of water is measured by the

water meter, or may be manually started by a front panel or remote Start input The batch size, up to 99,999,900 gallons, is

preset on the front panel, and the display counts down to zero Regeneration is stopped either after a predetermined amount

of time expires, or a front panel or remote Stop input is received The timeout, up to 9,999 seconds is set on the front panel
The PRC-20 is programmed by the installer to operate either in Auto or Manual mode In Auto mode, regardless of whether

regeneration was started by the batch count reaching zero, or by a Start input, the count will immediately return to the preset

amount and count down as pulses are received from the meter Regeneration will end when the timeout period elapses,

or when a Stop input occurs In Manual mode, the count will remain at zero, and regeneration will continue until a Stop

input occurs
To avoid simultaneous regeneration of multiple tanks, a lockout signal can prevent a controller from starting regeneration at

the end of a batch If a lockout is active when the batch counter reaches zero, or when a Start input is received, the controller

will remember to start regeneration as soon as the lockout signal is terminated Furthermore, the running batch count can be

adjusted on the front panel as another method of avoiding simultaneous regeneration
When power to the control is lost, the PRC-20 will store the running batch count in memory If used in the Auto mode, and a

regeneration cycle had been started when power was lost, it will also store the time remaining in the cycle The unit stores

these values in non-volatile memory, which requires no battery, and will retain these values
When power to the control is turned back on, the unit will either continue from where it is left off when power was lost,

or it will automatically initiate a regeneration cycle If the power up start input is disabled, the PRC-20 will simply continue

counting from the retained time value, and/or timing the regeneration cycle from the retained time value If the powerup

start input is enabled, the PRC-20 will start a regeneration cycle, just as if the batch had counted down to zero, or the operator

had manually started one

MOUNTING

The PRC-20 controller comes in a rugged, watertight polycarbonate enclosure intended for wall or panel mounting
When mounting the unit select a location which has adequate ventilation, protection against mechanical shock and

accessibility for operation and service

Operating Temperature: 32…122° F (0…50° C)

Operating Humidity:

Up to 85% non-condensing

Wall or Panel Mount

1 Using the appropriate mounting hardware, attach the back part of the housing to the mounting surface
2 Wire the unit according to

“Wiring” on page 7