Wiring, Terminal block layout, Ac power input – Badger Meter Water Conditioning User Manual

Page 7: L1 (hot) l2 (neutral) ground

Advertising
background image

WIRING

There are seven terminal blocks on the rear of the PRC-20 controller Three of them will require wiring, one may require wiring,

and three will not require any wires Do not use any of the unused terminals in the following diagrams for wiring points

Damage to the controller could result The three terminal blocks that require wiring are:

AC power input

Transmitter input

Regeneration relay output

Terminal Block Layout

Control inputs

Transmitter input

AC power input

Relay output

Not used

The control input terminal block will require wiring only

if a remote Start or Stop input is used, if a lockout input is

needed, or if power up start must be enabled
The remote Start and Stop inputs duplicate the functions of

the front panel Start and Stop buttons as described above

However, there are some differences to be aware of The

front panel Start and Stop buttons require a second press of

the button within ten seconds of the first press to initiate a

start or stop The rear terminal Start and Stop inputs initiate

the function immediately The front panel Start and Stop

buttons act as momentary switches, which means that

the action occurs when the button is pressed, and is not

repeated until the button is released and then pressed again

The rear terminal inputs act as maintained inputs

If the Start terminal is switched to ground, the regeneration output will turn on and remain on as long as the input is

grounded A Stop input will always override a Start input, for as long as the Stop input is connected to ground
In the Auto mode, the output timer will not start timing until the Start input switch is opened Therefore, it is normally

recommended that remote Start and Stop input switches be momentary, rather than maintained
Lock inputs are treated as maintained inputs, and maintained switches should be used Lockout occurs immediately when the

lock input is active, and ends when the lock input goes inactive There are several variations of lock inputs They are discussed

in detail in the control input wiring section below Since the power up start function will normally always be used or not used,

use a jumper wire to enable power up start, or leave the terminal open to disable power up start

AC Power Input

L1 (hot)

L2 (neutral)

Ground

85-265 VAC

47-63 Hz

20 VA

12-24 AWG

User Manual

Page 7

April 2013