2 Installation procedure

BU 0710 GB

11

2.2 Posicon I/O connection

The Posicon I/O special extension module (also referred to as XU,
EXtension Unit) is a system of positioning control for integration
into the frequency inverter. The positions which have been
programmed in advance will be exactly and dynamically
appproached on the basis of distance calculation.
Positions are captured by means of an incremental encoder and/or
an absolute value encoder.
The encoders may be installed either on the motor or on the load.
Step-up or step-down ratios can be adjusted at discretion.

Maximum connection cross section of the control lines:

Connector

Functions

Maximum cross section

X10.1

Output relay

1.0 mm

2

X10.2

Digital inputs

1.0 mm

2

X10.3

SSI input

1.0 mm

2

X10.4

Incremental encoder input

1.0 mm

2

PLEASE NOTE: All of the control voltages are related to the same reference potential!

The total allowable current rating of all individual power sources put together will be = 300mA max.

Floating contact or PLC output:
7.5 ... 33V

Digital inputs:

DIG IN 7 to 12
for position setting

Voltage supply:
5V,

∑ 300mA max.

Absolute value encoder input:
SSI, 24 bits

Incremental encoder input:
TTL, RS 422, 250kHz max.
500 – 5000 pulses/rev.

Voltage supply:
15V,

∑ 300mA max.

Output relay:

max. 2,0A
28V DC / 230V AC

27 DIG IN 7
28 DIG IN 8
29 DIG IN 9
30 DIG IN 10
31 DIG IN 11

40 GND /0V
63 SSI1 CLK+
64 SSI1 CLK-
65 SSI1 DAT+
66 SSI1 DAT-

41 VO +5V
40 GND /0V
51 ENC1 A+
52 ENC1 A-

05 REL3.1
06 REL3.2
07 REL4.1
08 REL4.2

X1
0.1

X1
0.2

X1
0.3

X1
0.4

32 DIG IN 12
42 VO +15V

53 ENC1 B+
54 ENC1 B-
55 ENC1 N+
56 ENC1 N-