4 Positioning parameters

BU 0710 GB

23

Parameter

Setting / Description / Note

Available with option

P612 (P)

Size of destination window

POS

0,1...100,0 rev

[ 0 ]

The destination window allows for ensuring a crawling motion towards the end of the
positioning operation. Inside the destination window the maximum rate of progression
depends on the setting made in parameter P104 (minimum frequency) rather than on the
maximum or setpoint frequency.

Important: If when setting up a destination window the minimum frequency set in

parameter P104 is 0Hz, the final position cannot be reached.

P613 (P)

..-01

..-63

Position array element

POS

-50000...50000.000 rev.

[ 0 ]

Array for the 63 different setpoint positions which can be selected in the "position array"
setpoint mode via the digital inputs or via a field bus.

P614 (P)

..-01

..-06

Position increment array element

POS

-50000...50000.000 rev.

[ 0 ]

Array for the 6 position increments which are selected in the "position increment array"
position setpoint mode via the digital inputs or via a field bus. With each change of signal from
"0" to "1" at the digital input involved, the value allocated to the digital input is added to the
position setpoint.

P615 (P)

Maximum position

POS

-50000...50000.000 rev.

[ 0 ]

Setpoints are limited to the value set here. When the actual position setpoint exceeds this
value, the error signal "E147" indicating that the maximum position was exceeded, becomes
active. When this parameter is set to 0, position monitoring is deactivated.

P616 (P)

Minimum position

POS

-50000...50000.000 rev.

[ 0 ]

Setpoints are limited to the value set here. When the actual position value drops below this
amount, the error signal "E148" indicating that the minimum position was exceeded, is
activated. Position monitoring is deactivated by setting this parameter to "0".

P617

Monitoring of position recognition

POS

0...1

[ 0 ]

This type of monitoring can be used with absolute value shaft encoders where a voltage
monitoring bit is available.

P618

Function digital input 7

POS

0...11

[ 1 ]

"Bit 0 position array / position increment array“ is the default setting

P619

Function digital input 8

POS

0...11

[ 2 ]

"Bit 1 position array / position increment array“ is the default setting

P620

Function digital input 9

POS

0...11

[ 3 ]

"Bit 2 position array / position increment array“ is the default setting

P621

Function digital input 10

POS

0...11

[ 4 ]

"Bit 3 position array / position increment array" is the default setting

P622

Function digital input 11

POS

0...11

[ 7 ]

"Bit 4 position array / position increment array“ is the default setting