1 assembly, Assembly, Table 6: example: "switch fi on and off + setpoint – NORD Drivesystems BU2100 User Manual

Page 17: Table 7: assembly instance, 4 communication and protocol

Advertising
background image

4 Communication and Protocol

BU 2100 GB-2213

17

Parameter

Setting value

Meaning

Parameter number

SK

180E …

SK 2xxE,
SK 54xE

SK

500E …

SK 535E

Maximum frequency

50.0

50 Hz

P105

P105

Actual bus value 1

1

Actual frequency

P543[-01]

P543

Function Bus setpoint 1

1

Setpoint frequency

P546[-01]

P546

Order to FI

Response from FI

Control word

Setpoint 1

Status word

Actual value

1

Explanation

- - -

- - -

0000h

0000h

- - -

- - -

xx40h

0000h

Switch-on of the mains voltage to the FI

047Eh

0000h

xx31h

0000h

Sets the FI in the status "Standby"

047Fh

2000h

xx37h

2000h

Sets the FI to the status "Operation
enabled" with the setpoint 50%.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 25 Hz.

0047Eh

2000h

xx31h

0000h

Sets the FI to "Standby" status. The
motor runs on its parameterised ramp up
to speed 0 and then the power is
switched off.

The FI is locked again and the motor is without current.

047Fh

1000h

xx37h

1000h

Sets the FI to the status "Operation
enabled" with the setpoint 25 %.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5 Hz.

Table 6: Example: "Switch FI on and off + setpoint"

4.2 Transfer of Data in the Bus System (I/O connections)

Process data is exchanged between the SK xUx-EIP bus module and the EtherNet/IP Master via I/O
connections. An "Exclusive Owner" connection can be opened, through which the setpoints and actual
values can be exchanged. In addition, two "Listen Only" connections can be opened, through which
the actual values of the FI can be read.

4.2.1 Assembly

Only process data, but no protocol information can be transmitted via the I/O Message Object.
Assignment of the relevant setpoints and actual values is performed via the Assembly Object. The
following table lists several pre-defined configurations (Instances).

Instance

Length
(Byte)

Meaning*

Device class
(SK ...)

Data length

100

12

STW + SW1 + SW2 + SW3 + SW4 + SW5

TU3-EIP,
TU4-EIP

Fixed

101

12

ZSW + IW1 + IW2 + IW3 + IW4 + IW5

TU3-EIP,
TU4-EIP

Fixed

110

50

Bus module outputs + four FIs
Structure for each FI:
STW + SW1 + SW2 + SW3 + SW4 + SW5

TU4-EIP

Variable

111

50

Module inputs + four FIs
Structure for each FI:
ZSW + IW1 + IW2 + IW3 + IW4 + IW5

TU4-EIP

Variable

* STW = Control word, ZSW = Status word, SW = Setpoint, IW = Actual value

Table 7: Assembly Instance