Module status, Status of digital input, Relay status – NORD Drivesystems BU2100 User Manual

Page 26

Advertising
background image

EtherNet/IP Bus module

– Supplementary manual options for NORD - Frequency Inverters

26

BU 2100 GB-2213

P173

Module Status

(Module status)

SK

EB…

SK TU3-

SK xU4-

16 bit

0 ... 0xFFFF

Operating status of the module.

Bit 0 =

Module ready for operation*

Bit 1 =

Cyclic communication*

Bit 2 =

Timeout by Ethernet bus*

Bit 3 =

Timeout (P151/P513)*

Bit 4 =

No communication with ASIC*

Bit 5 =

General configuration error*

Bit 6 =

System bus "BUS Warning"**

Bit 7 =

System bus "BUS OFF"**

Bit 8 =

FI 1 status

Bit 9 =

FI 1 status

Bit 10 =

FI 2 status**

Bit 11 =

FI 2 status**

Bit 12 =

FI 3 status**

Bit 13 =

FI 3 status**

Bit 14 =

FI 4 status**

Bit 15 =

FI 4 status**

* Except for ...IOE modules
** Except for SK TU3 versions

THe status of the frequency inverter is determined from a High bit and a Low bit: e.g. FI
1: High bit: Bit 9; low Bit: Bit 8

High Bit

Low Bit

Meaning

0

0

FI is offline

0

1

FI is not supported

1

0

FI is online

1

1

Bus error (PDO or SDO monitoring)

P174

Status of digital input

(Status of the digital inputs)

SK

EB…

SK xU4-

8 bit

0 ... 0xFF

Image of the switching status of the digital inputs of the module.

Bit 0 =

Digital input 1

Bit 1 =

Digital input 2

Bit 2 =

Digital input 3*

Bit 3 =

Digital input 4*

Bit 4 =

Digital input 5**

Bit 5 =

Digital input 6**

Bit 6 =

Digital input 7**

Bit 7 =

Digital input 8**

* Except for ... CU4- modules
** Only SK TU4-ECT, SK TU4-EIP, SK TU4-PNT and SK TU4-POL

P175

Relay Status

(Switching status of relay)

SK

EB…

SK TU4-

8 bit

0 ... 3

Image of the switching status of the relay outputs of the module.

Bit 0 =

Relay 1

Bit 1 =

Relay 2