NORD Drivesystems MI0300 User Manual

Page 18

Advertising
background image

Decentralised drive technology - from SK 300E to SK 200E

18

Migration Guide-GB-11.10.2012

SK 300E

Function / Meaning

SK 200E

Terminal bar

Terminal number

Terminal bar

Terminal number

SK 2x0E

SK 2x5E

SK TU2-DEV-...-(C)

DeviceNet
technology unit

Plug contacts

DeviceNet field bus option

SK TU4-DEV-(C)

DeviceNet module

Refer to BU 0280 for
connection assignments

Terminal bar

SK TI4-TU-BUS-(C)

M12 round plug

connectors

A coded

24V –B / Bus supply

1 + 2

DeviceNet High IN

3

DeviceNet High OUT

4

DeviceNet Low IN

5

Refer to BU 0080 for
connection
assignments

DeviceNet Low OUT

M12 Flanged connector

Plug connector

6

0V-B / Data ground Bus

7 + 8

SHLD / Bus cable shielding

9

PE / Bus cable bonding
conductor

10

SK TU2-CAO-..-(C)

Technology unit
Profibus DP

Plug contacts

CANopen field bus option

SK TU4-CAO-(C)

CANopen module

Refer to BU 0260 for
connection assignments

Terminal bar

SK TI4-TU-BUS-(C)

M12 round plug

connectors

A coded

24V –B / Bus supply

1 + 2

CAN High IN

3

CAN High OUT

4

CAN Low IN

5

Refer to BU 0060 for
connection
assignments

CAN Low OUT

M12 Flanged connector
Plug connector

6

0V-B / Data ground Bus

7 + 8

SHLD / Bus cable shielding

9

PE / Bus cable bonding
conductor

10

SK TU2-ASx-...-(C)

AS interface
technology unit

Plug contacts

AS interface field bus option /

SK 220E / 225E ...-(C) with
integrated ASI interface

SK TI4-x-22x-x-(C)
control terminal bar

Refer to BU 0200 for
connection assignments

SK TI4-x-
220-x-(C)

SK TI4-x-
225-x-(C)

M12 round plug

connectors

A coded

AS-i (+)

84

AS-i (-)

85

AUX GND

Not required

10

AUX 24V

Not required

10

Refer to BU 0020 for
the relevant technology
unit for the connection
assignments

ASI / Digital input 1

M12 Flanged connector
Plug connector

21

ASI / Digital input 2

22

ASI / Digital input 3

23

ASI / Digital input 4

24

ASI / Digital output 1

1

ASI / Digital output 2

3

-

11

Table 14: Overview of control terminals

10

The 24V supply is via the yellow AS interface cable (terminals 84 and 85)

11

Con only be implemented with an additional SK TU4-IOE-(C).