Installing, Connections, Installing the technology unit – NORD Drivesystems TI 275900150 User Manual

Page 3

Advertising
background image

EtherNet/IP Bus module – SK TU3-EIP

TI 275900150 - 4913

3

Installing

Note

Installing the technology unit

Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for
the intended modules.

Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly
to the frequency inverter.

The technology units must be installed as follows:

1. Switch off the mains voltage, observe the

waiting period.

2. Push the control terminals cover down

slightly or remove.

3. Remove the blank cover, by loosening the

release on the lower edge and pulling off
with an upward turning movement. If
necessary, the attachment screw next to the
release must be removed.

4. Hook the technology unit onto the upper edge slots and press in lightly until it engages.

Ensure full contact with the connector strip and fasten with the screws if necessary (separate
packet).

5. Close the control terminal cover again.

Pos : 12 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herN et/ IP/Ansc hlüss e [SK TU 3-EIP] @ 3\ mod_1363958898449_388. doc x @ 62382 @ 5 @ 1

Connections

The two Ethernet lines are connected exclusively via the two RJ45 sockets on the front. If the module
is the final subscriber on the line, one RJ45 socket can remain unoccupied.

( 1 ) RJ45 socket detail

( 2 ) Power supply detail

RJ45 Pin

Signal

Description

1

TX+

Transmission Data +

2

TX-

Transmission Data -

3

RX+

Receive Data +

6

RX-

Receive Data -

Terminal

Name

Description

45

+ 24 V

24 V supply

46

GND

Earth

Pos : 15 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herN et/ IP/Konfigurati on [ SK TU3- EI P] @ 3\ mod_1363947436882_388. doc x @ 62357 @ 5 @ 1