Parameters, Ethernet/ip bus module – sk tu3-eip – NORD Drivesystems TI 275900150 User Manual

Page 7

Advertising
background image

EtherNet/IP Bus module – SK TU3-EIP

TI 275900150 - 4913

7

Parameters

Frequency inverter: The following frequency inverter parameters must be adapted for setting up
communication between the frequency inverter and the bus module (for details see frequency
converter manual).

Parameter [-Array]

Meaning

Remarks

P120 [-01]

Option monitoring

"Auto“ (default setting)

Only SK xU4

P509

Control word source

SK TU3-… on SK 5xxE: "Ethernet TU”
SK xU4-… on SK 180/SK 2xxE: "System bus"

P510 [-01 … -02]

Setpoint source

"Auto“ (default setting)

P513

Time-out

Monitoring of the SK TU3 bus module

Only SK 5xxE

P543 [-01 …-03 (-05)]
and P543 … P545

Bus actual values (1 …3 (… 5))

Possible settings according to (P418)

P546 [-01 …-03 (-05)]
and P546 … P548

Bus target values (1 …3 (… 5))

Possible settings according to (P400)

P700 [-01] / P701

Current / last failures

Information parameters

P740 / P741

Process data bus In / Out

Information parameters

P745

Module version

Information parameters

Only SK TU3

P745

Module status

Information parameters

Only SK TU3

P748

CANopen / System bus status

Information parameters

Pos : 24 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herN et/ IP/Paramet er [ EIP Allgemein] @ 3\ mod_1363788177458_388.doc x @ 61890 @ @ 1

BUS module: The module provides a selection of appropriate parameters for setting or displaying
special operating values. Parameters can be adapted using the NORDCON software or an
SK PAR-3H / -3E parameter box. All parameters can still be read and written via Ether Net/IP by the
bus master.

Parameter [-Array]

Meaning

Remarks

-TU3-

-TU4-

-CU4-

P150

Set relays

Set DOUT directly or control via BUS

X

P151

External bus time-out

Monitoring of SK xU4 bus module;

X

X

P152

Factory setting

Reset module parameters

X

X

X

P153 [-01 …-02]

Minimum system bus
cycle

Reduction of the bus load on the system bus
caused by the module

X

X

P154 [-01 …-02]

Access to option card I/O

Administration of read and write rights to the IO of
the module

X

X

P160 [-01 … 04]

IP address

Alternative to setting the array value [-04]: DIP
switch,

à Value from DIP

-

switch has priority

X

X

X

P161 [-01 …-04]

IP subnet mask

X

X

X

P164 [-01 …-04]

IP Gateway

X

X

X

P165

Addressing mode

Setting "0" = value from DIP

-

switch or P160

(default setting)

X

X

X

P166

Process data transmit
format

Leave at default setting

X

X

X

P169

Password

X

X

X

P170 [-01 … -02]

Present errors

Displaying module errors

X

X

X

P171 [-01 … -03]

Software version

Firmware version / Revision

X

X

X

P172

Configuration

Module type

X

X

X

P173

Module status

Status of system bus or connected FI

X

X

X

P174

Status of digital inputs

Image of the switching status of DIN

X

X

P175

Digital output state

Image of the switching status of DOUT

X

P176 [-01 … ]

Process data bus In

Information parameter

X

X

X

P177 [-01 … ]

Process data bus Out

Information parameter

X

X

X

P178

Internal temperature

Information parameter

X

P180 [-01 … -02]

Active assembly

Information parameter

X

X

X

P181 [-01 … -06]

MAC address

Information parameter

X

X

X

P185 [-01 …-04]

Present IP address

Information parameter

X

X

X

P186 [-01 …-04]

Current IP subnet mask

Information parameter

X

X

X